High speed counter, Function of the frequency counter, Counter frequency and pulse shape – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 99: 5 1 f

Advertising
background image

Publication 1760-UM001D-EN-P - September 2005

Draw a Circuit Diagram with Pico 4-39

Function of the Frequency Counter

High Speed Counter

You can use the high-speed counters to count high frequency signals
reliably.

Pico provides two high-speed up/down counters, C13 and C14, for
use as required. The high-speed counter inputs are permanently
connected to the digital inputs I1 and I2. These counter relays allow
you to count events independently of the cycle time.

The high-speed counters allow you to enter an upper threshold value
as a comparison value. The C13 and C14 high-speed counters are not
dependent on the cycle time.

Counter Frequency and Pulse Shape

The maximum counter frequency is 1 kHz.

The signals must be square waves. We recommend a mark-to-space
ratio of 1:1.

If this is not the case: The minimum mark-to-space ratio is 0.5 ms.

1

2

3

t

g

t

g

t

g

t

g

t

g

t

g

t

g

t

g

4

5

t

g

A

B

C

D

1: Counter input I3 or I4.
2: Upper Setpoint.
3: Enable coil CC...
4: Reset coil RC...
5: Contact (make contact) C... upper setpoint value reached.
tg: Gate time for the frequency measurement.

• Range A: The counter is enabled. Contact C15 (C16)

switches after a frequency above the setpoint was
measured for the first time.

• Range B: If the actual value falls below the setpoint,

the contact is reset. The removal of the enable signal
resets the actual value to zero.

• Range C: The counter is enabled. After a frequency

above the setpoint was measured for the first time,
contact C15 (C16) switches.

• Range D: The reset coil resets the actual value to zero.

t

min

0.5

1

f

max

---------

×

=

t

min

= minimum time of the pulse or pause duration

f

max

= maximum count frequency (1 kHz)

Advertising