Draw a Circuit Diagram with Pico 4-61

How Does the Shift Register Work?

The shift pulse is switched on for exactly one cycle. To do this, the
shift pulse is generated by evaluating the change from I1 ‘off’ to I1
‘on’ - the rising edge. This allows the shift register to only shift once
regardless of how long I1 remains true.

When I1 is switched on for the first time, marker relay contact M7 is
off and the break contact is closed during the first pass through the
program. Thus, the series circuit consisting of I1, break contact M7
(closed) and M8 is turned on. Although M7 is switched on, this does
not yet affect contact M7.

The contact of M8 (make contact) was still open during the first scan
so a shift pulse is not yet generated. When the relay coil M8 is
activated, Pico transfers the result to the contacts.

In the second scan, break contact M7 opens. The series circuit is now
open. The contact M8 is switched on from the result of the first scan.
Now, all the storage positions are either set or reset in accordance
with the series circuit.

M2

Second storage position

M3

Third storage position

M4

Fourth storage position

M7

Marker relay for one-shot pulse

M8

One-shot pulse used for shift pulse

Item

Function

I1-M7-------{M8

---------{M7

M8-M3-------SM4

M3-------RM4

M2-------SM3

M2-------RM3

M1-------SM2

M1-------RM2

I2-------SM1

I2-------RM1

I3----------RM1

RM2

RM3

RM4

Generate shift pulse

Set 4th storage position

Set 3rd storage position

Set 2nd storage position

Set 1st storage position

Clear 4th storage position

Clear 3rd storage position

Clear 2nd storage position

Clear 1st storage position

Clear all storage position