Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 37

Advertising
background image

Publication 1760-UM001D-EN-P - September 2005

Installation 2-13

For inductive dc load devices, a diode is suitable. A 1N4004 diode is
acceptable for most applications. A surge suppressor can also be used.
See the table on page 2-14 for recommended suppressors.

As shown in the illustration below, these surge suppression circuits
connect directly across the load device.

Surge Suppression for Inductive ac Load Devices

Output Device

Output Device

Output Device

Varistor

RC Network

Surge
Suppressor

Surge Suppression for Inductive dc Load Devices

Output Device

Diode

_

+

(A surge suppressor can also be used.)