Retention 7-11

Off-Delayed, Off-Delayed Switching with Random Time Range, Retentive

Task:
No-load running of a conveyor belt. (Same as the previous example
except implemented using an off-delay timer)

Contacts and relays used:

I2 and I3 are converted to one-shot pulses by T6/T7. Only the
actuation of the push-button is recognized. In the above example, T7
does not have to be retentive.

Signal diagram:

U = Supply voltage

Coil

Function

T6/T7

Single pulse

I2

Start conveyor belt

Q1

Conveyor belt motor

I3

Stop conveyor belt

M16

Stop selected

T8

Remaining time

I2---------TT6

T6-T8------SQ1

M16

I3---------TT7

T7--------SM16

M16---------TT8

T8---------RQ1

RM16

30.00

TRG

RES

S

{

T8

+

Circuit Diagram:

Parameters Entered:

Time setting for T6, T7

U

I2/T6

Q1

I3

M16

t

1

t

2

T8

t + t = 30s

1

2