Publication 1760-UM001D-EN-P - September 2005

2-18 Installation

Example Using 1760-IB12XOB8

Connect 12 V dc Inputs

Use input terminals I1 to I8 to connect push-buttons, switches, or 3 or
4-wire proximity switches. Given the high off-state leakage current, do
not use 2-wire proximity switches.

Example Using 1760-L12DWD

Input

Specification

Input Signal Voltage Range

OFF signal: 0 to 4V dc

ON signal: 8V to 15.6V dc

Input Current

I1 to I6, I9 and I10: 3.3 mA at 12V dc

I7 and I8, I11 and I12: 1.1 mA at 12V dc

+24V dc

0V

F1

NC

NC

R2

R3

R4

R5

R6

R7

R8

R1

R9 R10 R11 R12 +24V

24V dc

Inputs x 24V dc

COM

+12V dc

0V

1A

12V dc

+12 V COM

I2

I3

I4

I5

I6

I7

I8

I1

Inputs x 12V dc