Inputs, Ac models – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 195

Advertising
background image

Publication 1760-UM001D-EN-P - September 2005

Specifications A-5

Inputs

AC Models

Specification

1760-L12NWN
1760-L12NWN-ND

1760-L18NWN-EX
1760-L18NWN-EXND

Digital inputs 24V ac

Number

8

12

Status display

LCD (if provided)

LCD (if provided)

Electrical isolation

To power supply

No

No

Between Inputs

No

No

to the outputs

Yes

Yes

Rated voltage (sinusoidal)

off state

0 to 6V ac

0 to 6V ac

on state

14 to 26.4V ac

14 to 26.4V ac

Rated frequency

50/60 Hz

50/60 Hz

Input current
I1 to I6
(1760-L18NWN-xx also I9 to I10)

4 mA at 24V ac 50 Hz

4 mA at 24V ac 50 Hz

Input current
I7, I8
(1760-L18NWN-xx also I11 and
I12)

2 mA at 24V ac 50 Hz,
2 mA at 24V

2 mA at 24V ac 50 Hz,
2 mA at 24V

Delay time I1 to I8 and I9 to I12 (1760-L18-NWN-xx), From 0 to 1 and from 1 to 0

Debounce ON

80 ms (50 Hz), 66

.66

ms

(60 Hz)

80 ms (50 Hz), 66

.66

ms

(60 Hz)

Debounce OFF

20 ms (50 Hz), 16

.66

ms

(60 Hz)

20 ms (50 Hz), 16

.66

ms

(60 Hz)

Max. permissible cable length (per input)

I1 to I8 and
1760-L18NWN-xx I9 to I10

40m (131 ft)

Advertising