7-10 Retention

Contacts and relays used:

I2 and I3 are converted to one-shot pulses by T6 / T7. Only the
actuation of the push-button is recognized. Should they remain
constantly pressed, malfunctions would occur.

In the above example,

T7 does not have to be retentive.

I2 is a normally open push button, and I3 is a normally closed push
button. A normally closed push button is used for the STOP
CONVEYOR signal so that in the event of a loose or broken wire, the
conveyor automatically stops.

Signal diagram:

U = Supply voltage

The make contact of T8 closes for one Pico cycle and resets M16, Q1.

Coil

Function

T6/T7

One shot timers

I2

Start conveyor belt

Q1

Conveyor belt motor

I3

Stop conveyor belt

M16

Stop selected

T8

Remaining time

I2---------TT6

T6---------SQ1

M16

I3----------TT1

T1---------SM16

M16---------TT8

T8----------RQ1

RM16

30.00

TRG

RES

T8

+

X

S

{

Circuit Diagram:

Parameters Entered:

Time setting for T6, T7

U

I2/T6

Q1

I3

M16

T8

t

1

t

2

t + t = 30s

1

2