4-54 Draw a Circuit Diagram with Pico

Power Flow Display

Jumped ranges are indicated by the coils in the power flow display.
All coils after the jump coil are shown with the symbol of the jump
coil.

Contacts and relays used:

EXAMPLE

A selector switch allows two different sequences to
be set.

• Sequence 1: Switch on Motor 1 immediately.
• Sequence 2: Switch on Guard 2, Wait time, then

switch on Motor 1.

Coil

Function

I1

Sequence 1

I2

Sequence 2

I3

Guard 2 moved out

I12

Motor-protective circuit-breaker switched on

Q1

Motor 1

Q2

Guard 2

T1

Wait time 30.00 s, on-delayed

D1

Text ‘Motor-protective circuit-breaker tripped’

I1----------{:1

I2----------{:2

:1

------------{Q1

RQ2

------------{:8

:2----------{Q2

Q2-I3-------TT2

T2----------{Q1

:8

I12---------{D1

I1----------{:1

I2-----------:2

:1

------------

{Q1

RQ2

------------

{:8

:2----------{Q2

Q2-I3-------TT2

T2----------{Q1

:8

I12---------{D1

Circuit Diagram:

Power Flow Display: I1 selected:

Range from jump label 1
processed.

Jump to label 8.
Range to jump label 8 skipped.

Jump label 8, circuit diagram
processed from this point on.