Examples

On-Delayed, Switching On-Delayed with Random Range, Retentive

Task 1 (On-Delayed):
A motor must start up 30 seconds after an enable signal is given.

This task is implemented using an input device which retains its '1'
state on power-up.

Contacts and relays used:

Signal diagram:

U = Supply voltage

I1 must be activated when the power is turned back on.

Task 2
A conveyor belt is to be run empty. This no-load running is
implemented by using a time relay to keep the belt running following
the STOP BELT command until the preset time has elapsed. If this
procedure is interrupted by an interruption of power, the belt is only
permitted to run empty after power-up for the remainder of the preset
time period. This task is implemented using retentive markers.

Coil

Function

I1

Motor Enable

Q2

Motor

T8

Delay time

I1---------TT8

T8------{Q2

30.00

TRG

RES

X

S

{

T8

+

Circuit Diagram:

Parameter Display:

t + t = 30s

U

I1

T8

t

1

t

2

1

2