Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 140

Advertising
background image

Publication 1760-UM001D-EN-P - September 2005

6-8 Pico System Settings

Variable Parameters for Function Relays

You can modify the relay parameters used in the circuit diagram in
three different ways:

• All circuit diagram parameters can be adjusted in Stop mode via

the circuit diagram.

• Setpoints can be modified in Run mode via the circuit diagram.
• Setpoints can be modified via the PARAMETER menu.

The following setpoints can be modified

• The timer setpoints for timing relays
• The counter setpoints of counter relays
• The day and ON/OFF times of time switches
• The comparison setpoint of analog comparators.

In Run mode, Pico operates with a new setpoint as soon has it is
modified in the parameter display and saved.

Example: Modify Switching Times for Outside Lighting

The outside lighting of a building is automatically switched on from
19:00 to 23:30 (7:00 pm to 11:30 pm) Mondays to Fridays in the Pico
program.

The parameter set for the time switch function relay 1 is saved in
channel ’A’ and looks like this.

The outside lighting is now required to also turn on between 19:00
and 22:00 on Saturdays.

1. Select PARAMETER from the main menu.

The first parameter set is displayed.

2. Use up or down arrows to scroll through the parameter sets until

channel A of time switch 1 is displayed.

3. Press the up arrow to select the next empty parameter set, in this

case channel B of time switch 1.

The current time is 15:21.

MO-FR

15:21

19:00

23:30

D

+

ON

OFF

1 A

--

15:21

00:00

00:00

D

+

ON

OFF

1 B