CIRCUTOR CVM-B Series User Manual

Page 158

Advertising
background image

5�6�16�2�-

Impulse mode of transistor digital output

When selecting the impulse mode,

figure 132,

the configuration parameters are:

The variable code that controls the transistor.

The energy meter factor.

The high and low impulse period.

figure 132: Configuration screen of transistor digital outputs (impulse mode).

The parameter selected is indicated in white.

It is possible that the unit may measure energy exceeding its configuration. Make

sure the energy pulses correspond to the maximum energy level admitted by the

installation.

To program the transistor digital output, after configuring the

variable code and the pulse time

(with the

low period and high period parameters), the following formula provides a method for

calculating the number of output pulses according to the generated energy so that the pulses

do not accumulate.

3600 *

Pe / PT > MP → PE = MP * TP / 3600

Where:

MP : Maximum power of the installation in W.

Pe: Pulse energy in Wh ( energy meter factor )

TP : low period + high period, in seconds.

For example: If the installation can consume 100kW, a suitable configuration could be pulses

of 10W (

energy meter factor) with a high and low period of 50 ms.