6�3�7�5�- Measurement connection mode

This parameter occupies 1 register.

Table 35: Modbus memory map: Configuration variables (Measurement connection mode).

Measurement connection mode

Configuration variable

Address

Valid data window

Default value

Measurement connection mode

2A9D

0: Single-phase

1: Two-phase

2: Two-phase with Neutral

3: Three-phase

4: Three-phase with Neutral

5: Aron

4

6�3�7�6�- Ratio of voltage and current transformers

These parameters occupy 2 registers each.

Table 36:Modbus memory map: Configuration variables (transformation ratios)

Transformation ratios

Configuration variable

Address

Valid data window

Default value

Primary voltage

(1) (2)

2710-2711

1 - 500000

1

Secondary voltage

(1)(4)

2712-2713

1 - 9999

10

Primary current

(2)

2714-2715

Minimum value:

1

Maximum value:

../1A y ../5 A:

10000

../ 0.250 A:

1500

5

Secondary current

2716-2717

1 : ../1A

5 : ../5 A

250 : ../ 0.250 A

5

Primary neutral current

2718-2719

1 - 10000

5

Secondary neutral current

271A-271B

0: Calculated current

1 : ../1A

5 : ../5 A

5

Rated voltage

(3)

271C-271D

Minimum value:

(Rated Voltage / Voltage ratio

(5)

)

50

Maximum value:

(Rated Voltage / Voltage ratio

(5)

)

1000

230.00

(1)

Primary voltage/Secondary voltage must not exceed the value 9999.

(2)

Primary voltage * Primary current must not exceed the value 60MW.

(3)

It has 2 decimals.

(4)

The secondary voltage has 1 decimal.

(5)

The voltage ratio is the ratio between the primary and secondary voltage.

Note: The 14 registers must be written at once (as a group), otherwise it will respond with an

error.

190

CVM-B100 - CVM-B150