Table 55 ( Continuation) : Configuration of custom screens: Variables�

Variables parameter

Variable

Value

Variable

Value

Apparent Power

0x000A

CO

2

Emissions

0x0018

Power Factor

0x000B

Cost

0x0019

Cosine

φ

0x000C

Empty (no parameters)

0x001A

Voltage THD

0x000D

Table 56: Configuration of custom screens: Phases.

Phases Parameter

Phase

Value

Phase

Value

L1

0x0000

L1-L2

0x0000

L2

0x0001

L2-L3

0x0001

L3

0x0002

L3-L1

0x0002

Total III

0x0003

L1-L2-L3

0x0003

LN

0x0004

Table 57:Configuration of custom screens: Tariffs

Tariffs Parameter

(7)

Tariff

Value

Tariff

Value

Tariff 1

0x0000

Tariff 3

0x0002

Tariff 2

0x0001

Total value of 3 tariffs

0x0003

(7)

If the variable has no tariff option, 00 will be sent.

6�3�7�19�- Manual programming of alarms

These parameters occupy 1 register each.

Table 58: Modbus memory map: Configuration variables (manual programming of alarms).

Manual programming of alarms

Configuration

variable

Address

Valid data window

Default

value

Output 1

Relay

Output 2

Relay

Output 1

Transistor

Output 1

Transistor

Programming status

(1)

4F20

4F34

4EF8

4F0C

0: Automatic

1:Manual

0

Value

4F21

4F35

4EF9

4F0D

0: Open

1:Closed

0

(1)

When programming the

Programming status manually , set the output for the relays and transistors manually,

using the

Value parameter. The configuration of the relay and transistor digital outputs programmed in the unit

no longer works.
The relays and transistors work in automatic mode according to the configuration programmed in the unit.

Note: The 2 registers must be written at once (as a group), otherwise it will respond with an

error.

200

CVM-B100 - CVM-B150

Instruction Manual