Table 55 – CIRCUTOR CVM-B Series User Manual

Page 199

Advertising
background image

Table 54: Modbus memory map: Configuration variables (Configuration of the parameter customisation screens)

Configuration of the parameter customisation screens

Configuration variable

Address

Valid data

margin

4 parameter screens

Screen 1

Screen 2

Screen 3

Screen 4 Screen 5

Parameter 1: Variable

2A30

2A40

2A50

2A60

2A70

Table 55

Parameter 2: Variable

2A31

2A41

2A51

2A61

2A71

Table 55

Parameter 3: Variable

2A32

2A42

2A52

2A62

2A72

Table 55

Parameter 4: Variable

2A33

2A43

2A53

2A63

2A73

Table 55

Parameter 1: Phase

2A34

2A44

2A54

2A64

2A74

Table 56

Parameter 2: Phase

2A35

2A45

2A55

2A65

2A75

Table 56

Parameter 3: Phase

2A36

2A46

2A56

2A66

2A76

Table 56

Parameter 4: Phase

2A37

2A47

2A57

2A67

2A77

Table 56

Parameter 1:

(1)

Consumption or Generation

2A38

2A48

2A58

2A68

2A78

0: Consumption

1: Generation

Parameter 2:

(1)

Consumption or Generation

2A39

2A49

2A59

2A69

2A79

0: Consumption

1: Generation

Parameter 3:

(1)

Consumption or Generation

2A3A

2A4A

2A5A

2A6A

2A7A

0: Consumption

1: Generation

Parameter 4:

(1)

Consumption or Generation

2A3B

2A4B

2A5B

2A6B

2A7B

0: Consumption

1: Generation

Parameter 1: Tariff

2A3C

2A4C

2A5C

2A6C

2A7C

Table 57

Parameter 2: Tariff

2A3D

2A4D

2A5D

2A6D

2A7D

Table 57

Parameter 3: Tariff

2A3E

2A4E

2A5E

2A6E

2A7E

Table 57

Parameter 4: Tariff

2A3F

2A4F

2A5F

2A6F

2A7F

Table 57

(1)

A 0 must be sent in the energy parameters where the consumption or generation option does not exist.

Note: The 80 registers must be written at once (as a group), otherwise it will respond with an

error. They can be read separately.

The unit has 3 types of screens to customise:

1 parameter displayed on screen.

3 parameters displayed on screen.

4 parameters displayed on screen.

Each of these types of screen has 5 different screens to customise.

Table 55: Configuration of custom screens: Variables.

Variables parameter

Variable

Value

Variable

Value

Phase-Neutral Voltage

0x0000

Current THD

0x000E

Neutral Voltage

0x0001

Maximum Current Demand

0x000F

Phase-Phase Voltage

0x0002

Maximum Active Power Demand

0x0010

Current

0x0003

Maximum Apparent Power Demand

0x0011

Neutral Current

0x0004

Active Energy

0x0012

Frequency

0x0005

Inductive Reactive Energy

0x0013

Active power

0x0006

Capacitive Reactive Energy

0x0014

Inductive Reactive Power

0x0007

Total Reactive Energy

0x0015

Capacitive Reactive Power

0x0008

Apparent Energy

0x0016

Total Reactive Power

0x0009

No. of hours of active tariff

0x0017

199

Instruction Manual

CVM-B100 - CVM-B150