6�- INTegRATeD COMMUNICATIONS

The

CVM-B units have one RS-485 communications port.

The unit has as standard two communications protocols:

MODBUS RTU ® and BACnet.

The protocol and configuration parameters are selected on the setup menu. (

“5.6.18.-

In-

tegrated communications.”

).

The unit is factory configured with the

MODBUS protocol.

6.1.- CONNECTIONS

The RS-485 cable should be wired with a twisted pair cable with mesh shield (minimum 3

wires), with a maximum distance between the

CVM-B and the master unit of 1200 metres.

A maximum of 32

CVM-B units can be connected to this bus.

Use an intelligent converter to establish communications with the master unit.

B ( - )

RS-232 / USB / Ethernet / Profibus ...

PC

B ( - )

A ( + )

RS-485

S

A(+) B(-) S

A(+) B(-) S

RS-485

RS-232

USB

Ethernet

Profibus

...

figure 141: RS-485 Connection diagram�