CIRCUTOR CVM-B Series User Manual

Page 195

Advertising
background image

6�3�7�14�- Digital inputs

The

Input Name configuration variable occupies 4 registers.

The

Units configuration variable occupies 3 registers.

All other variables

occupy 1 register each.

Table 46:Modbus memory map: Configuration variables (Digital Inputs).

Configuration of Digital Inputs

Configuration variable

Address

Valid data window

Default

value

Input 1

Input 2

Mode

4FB0

4FBC

-1: Tariff

0: Logic state

> 0:Impulses

(1)

0

Logic (Logic state)

4FB1

4FBD

0: positive

1: Negative

0

No. of decimals (Impulses)

4FB2

4FBE

0 to 5

0

Not used

4FB3

4FBF

0

0

Input name (impulses)

(2)

4FB4 - 4FB7 4FC0 - 4FC3

8 characters

“INPUT”

Units (Impulses)

(2)

4FB8 - 4FBA 4FC4 - 4FC6

6 characters

-

(1)

When programming a value of more than 1, programme the impulse operating mode and energy meter factor

for this mode simultaneously.

(2)

the characters must be sent in hexadecimal.

Note: The 11 registers must be written and read at once (as a group), otherwise it will respond

with an error.

6�3�7�15�- Integrated communications

These parameters occupy 1 register each.

Table 47:Modbus memory map: Configuration variables (Communications)

Communications

Configuration variable

Address

Valid data window

Default value

Protocol

2738

0 : Modbus , 1: BACnet

0

Peripheral number

2739

0 to 255

1

Speed

273A

0: 1200 - 1: 2400 - 2: 4800

3: 9600 - 4: 19200 - 5: 38400 -

6: 57600 - 7: 76800 - 8: 115200

4

Parity

273B

0 : No parity

1: Odd parity

2: Even parity

0

Length

273C

1: 8 bits

1

Stop bits

273D

0: 1 stop bit

1: 2 stop bits

0

Note: The 6 registers must be written at once (as a group), otherwise it will respond with an

error.

195

Instruction Manual

CVM-B100 - CVM-B150