6.3.7.- Unit configuration variables

The following functions are implemented for these variables:

function 0x04: reading registers.

function 0x10: Writing multiple registers.

NB: The programming values must be written in hexadecimal.

It is necessary to change the screen when a setup change is made for communi-

cations in order for the changes take effect in the display.

6�3�7�1�- Date and time

These parameters occupy 1 register each.

Table 30:Modbus memory map: Configuration variables (Date and Time).

Date and Time

Configuration variable

Address

Valid data window

Default value

Year

283C

2013 to 2076

-

Month

283D

1 to 12

-

Day

283E

1 to 31

-

Time

283F

0 to 23

-

Minutes

2840

0 to 59

-

Seconds

2841

0 to 59

-

Note: The 6 registers must be written at once (as a group), otherwise it will respond with an

error

.

6�3�7�2�- Time zone

These parameters occupy 1 register each.

Table 31:Modbus memory map: Configuration variables (time zone).

Local time configuration

Configuration variable

Address

Valid data window

Default value

Configuration of local time

2A9E

Table 32

0

Time

2A9F

0: Winter

1:Summer

0

Note: The 2 registers must be written at once (as a group), otherwise it will respond with an

error.