CIRCUTOR CVM-B Series User Manual

Page 225

Advertising
background image

Table 79: Modbus memory map: Status of relay digital outputs (Table 2)�

Status of relay digital outputs: Slot 1

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Latch

C670

C684

C698

C6AC

C6C0

C6D4

C6E8

C6FC

Connection delay

C672

C686

C69A

C6AE

C6C2

C6D6

C6EA

C6FE

Disconnection delay

C673

C687

C69B

C6AF

C6C3

C6D7

C6EB

C6FF

Alarm activation date: Year

C674

C688

C69C

C6B0

C6C4

C6D8

C6EC

C700

Alarm activation date: Month

C675

C689

C69D

C6B1

C6C5

C6D9

C6ED

C701

Alarm activation date: Day

C676

C68A

C69E

C6B2

C6C6

C6DA

C6EE

C702

Alarm activation time: Time

C677

C68B

C69F

C6B3

C6C7

C6DB

C6EF

C703

Alarm activation time: Minutes

C678

C68C

C6A0

C6B4

C6C8

C6DC

C6F0

C704

Alarm activation time: Seconds

C679

C68D

C6A1

C6B5

C6C9

C6DD

C6F1

C705

Not used

C67A

C68E

C6A2

C6B6

C6CA

C6DE

C6F2

C706

Not used

C67B

C68F

C6A3

C6B7

C6CB

C6DF

C6F3

C707

Status

C67C

C690

C6A4

C6B8

C6CC

C6E0

C6F4

C708

Alarm status

C67D

C691

C6A5

C6B9

C6CD

C6E1

C6F5

C709

Note: The 14 registers must be written at once (as a group), otherwise it will respond with an

error.

Table 80: Modbus memory map: Status of relay digital outputs (Table 3)�

Status of relay digital outputs: Slot 2

Configuration variable

Address

Output

1

Output

2

Output

3

Output

4

Output

5

Output

6

Output

7

Output

8

Latch

CA58

CA6C

CA80

CA94

CAA8

CABC

CAD0

CAE4

Connection delay

CA5A

CA6E

CA82

CA96

CAAA

CABE

CAD2

CAE6

Disconnection delay

CA5B

CA6F

CA83

CA97

CAAB

CABF

CAD3

CAE7

Alarm activation date: Year

CA5C

CA70

CA84

CA98

CAAC

CAC0

CAD4

CAE8

Alarm activation date: Month

CA5D

CA71

CA85

CA99

CAAD

CAC1

CAD5

CAE9

Alarm activation date: Day

CA5E

CA72

CA86

CA9A

CAAE

CAC2

CAD6

CAEA

Alarm activation time: Time

CA5F

CA73

CA87

CA9B

CAAF

CAC3

CAD7

CAEB

Alarm activation time: Minutes

CA60

CA74

CA88

CA9C

CAB0

CAC4

CAD8

CAEC

Alarm activation time: Seconds

CA61

CA75

CA89

CA9D

CAB1

CAC5

CAD9

CAED

Not used

CA62

CA76

CA8A

CA9E

CAB2

CAC6

CADA

CAEE

Not used

CA63

CA77

CA8B

CA9F

CAB3

CAC7

CADB

CAEF

Status

CA64

CA78

CA8C

CAA0

CAB4

CAC8

CADC

CAF0

Alarm status

CA65

CA79

CA8D

CAA1

CAB5

CAC9

CADD

CAF1

Note: The 14 registers must be written at once (as a group), otherwise it will respond with an

error.

225

Instruction Manual

CVM-B100 - CVM-B150

Advertising