Digital analogue inputs/outputs – CIRCUTOR CVM-B Series User Manual

Page 311

Advertising
background image

10.3.- DIGITAL ANALOGUE INPUTS/OUTPUTS

general features

Maximum power of the module

3W

Analogue outputs

Quantity

8

Maximum internal voltage

12 V

Linearity

<1%

DAC resolution

4096 dots

Analogue outputs in current mode

Nominal output range

0-20 mA or 4-20 mA (Programmable)

Maximum load resistor

300 Ω

Analogue outputs in voltage mode

Nominal output range

0-10 V

Minimum load resistor

5000 Ω

Analogue inputs

Quantity

4

Type of measurement

Current

Nominal input range

0-20 mA or 4-20 mA (Programmable)

Accuracy

<1%

Input impedance

150 Ω

Maximum acceptable input current

22 mA

environmental features

Operating temperature

-10ºC ... +50ºC

Storage temperature

-20ºC ... +80ºC

Relative humidity (without condensation)

5 ... 95%

Maximum altitude

2000 m

Protection degree

IP30

Mechanical features

Dimensions (mm)

figure 215 and figure 216

Weight

80 g

enclosure

V0 self-extinguishing plastic

Assembly

Panel

Standards

Safety requirements for electrical equipment for measurement, control

and laboratory use

IEC 61010: 2010

electromagnetic compatibility (CeM)� Part 6-2: generic standards� Immu-

nity for industrial environments�

UNE-EN 6100-6-2:2006

electromagnetic compatibility (CeM)� Part 6-4: generic standards� emis-

sions standard for industrial environments�

UNE-EN 6100-6-4:2007

Coordination of the insulation of units installed in low voltage systems

(networks)

IEC 664: 2007

Information technology equipment� Radio disturbance characteristics�

Limits and methods of measurement�

UNE-EN 55022

311

Instruction Manual

CVM-B100 - CVM-B150

Advertising