CIRCUTOR CVM-B Series User Manual

Page 203

Advertising
background image

6�3�8�5�2�- Transistor digital outputs

The

Latch variable occupies 2 registers.

All other variables

occupy 1 register each.

Table 64: Modbus memory map: Alarm status: Transistor digital outputs�

Alarm status: Transistor digital outputs

Configuration variable

Address

Valid data window

Alarm

Impulse

output

Output 1

Output 2

Alarm

Impulse

output

Latch

(1)

kWh or Wh

7530-7531 7544-7545

0: unlock alarm

1: locked alarm

kWh or Wh energy

meter

Delay in the

connection

(2)

Wh or mWh

7532

7546

Energy meter which

indicates the value

of the connection

delay variable (ON)

Wh or mWh energy

meter

Delay in the

disconnection

(2)

Energy meter

factor

7533

7547

Energy meter which

indicates the value

of the disconnec-

tion delay variable

(OFF)

Energy meter factor

meter

Alarm activation date:

Year

(2)

-

7534

7548

2013 to 2076

-

Alarm activation date:

Month

(2)

-

7535

7549

1 to 12

-

Alarm activation date:

Day

(2)

-

7536

754A

1 to 31

-

Alarm activation time:

Hour

(2)

-

7537

754B

0 to 23

-

Alarm activation time:

Minutes

(2)

-

7538

754C

0 to 59

-

Alarm activation time:

Seconds

(2)

-

7539

754D

0 to 59

-

Not used

Not used

753A

754E

-

-

Not used

Not used

753B

754F

-

-

Status

(2)

753C

7550

0: No alarm,

1: Active alarm

Alarm status

(2)

753A

754E

0: No alarm,

1: Pre-alarm,

2: Connection or disconnection delay,

3: Alarm,

4: Impulses,

(1)

If the latch option has been programmed in an alarm and it has been activated, the alarm will be unlocked with

this option.

(2)

For these variables only

function 0x04 is implemented: reading registers.

Note: The 14 registers must be written at once (as a group), otherwise it will respond with an

error.

203

Instruction Manual

CVM-B100 - CVM-B150