Technical features – CIRCUTOR CVM-B Series User Manual

Page 305

Advertising
background image

9�- TeCHNICAL feATUReS

AC power supply

Rated voltage

85 ... 265 V ~

frequency

50 ... 60Hz

Consumption

CVM-B100

CVM-B150

6... 8 VA

7...12 VA

Installation category

CAT III 300 V

DC Power supply

Rated voltage

20 ...120 V

120 ...300 V

Consumption

CVM-B100 CVM-B150 CVM-B100 CVM-B150

5 ... 6 W

7 ... 8 W

3 ... 4 W

4... 7 W

Installation category

CAT III 300 V

Voltage measurement circuit

Voltage measurement margin

20 ... 600 V ~

frequency measurement margin

40 ... 70 Hz

Input impedance

1.2 MΩ

Minimum measurement voltage (Vstart)

10 V ~

Maximum voltage input consumption

0.15VA

Installation category

CAT III 600 V

Current measurement circuit

Nominal current (In)

.../5A , .../1A or .../0.250 A

Phase current measurement margin

In: ���/5A

In: ���/1A

In: ���/0�250A

0.01...10A

0.01...2A

0.01 ...0.5A

Neutral current measurement margin

���/5A

���/1A

���/A (calculated)

0.02 ...10A

0.02...2A

0.02 ... 10A (

In: ���/5A)

0.02 ... 2A (

In: ���/1A)

0.02 ... 0.5A (

In: ���/0�250A)

Maximum current, impulse < 1s

100 A

Minimum measurement current (Istart)

0.01 A

0.01 A

0.01 A

Maximum current input

consumption

0.9 VA

Installation category

CAT III 600 V

Accuracy of measurements (in accordance with the IeC 61557-12 standard for PMD SD/SS)

���/5A

���/1A

���/0�250A

Voltage measurement

Class 0.2 ± 1 digit

(20 ...600 V~)

Class 0.2 ± 1 digit

(20 ...600 V~)

Class 0.2 ± 1 digit

(20 ...600 V~)

Neutral voltage measurement

Class 0.5 ± 1 digit

(50 ...600 V~)

Class 0.5 ± 1 digit

(50 ...600 V~)

Class 0.5 ± 1 digit

(50 ...600 V~)

Phase current measurement

Class 0.2 ± 1 digit

(0.05 ...8A)

Class 0.2 ± 1 digit

(0.01 ...1.2 A)

Class 0.2 ± 1 digit

(0.01 ...0.3 A)

Neutral current measurement

Class 1 ± 1 digit

(0.05 ...6A)

Class 1 ± 1 digit

(0.05 ...1.2 A)

Class 1 ± 1 digit

(Calculated)

Measurement of active and apparent

power (Vn 230/110 V~)

Class 0.5 ± 1 digit

(0.05 ...6 A)

Class 0.5 ± 1 digit

(0.01 ...1.2 A)

Class 0.5 ± 1 digit

(0.01 ...0.3 A)

Reactive power measurement

(Vn 230/110 V~)

Class 1 ± 1 digit

(0.05 ...6 A)

Class 1 ± 1 digit

(0.01 ...1.2 A)

Class 1 ± 1 digit

(0.01 ...0.3 A)

305