CIRCUTOR CVM-B Series User Manual

Page 218

Advertising
background image

7�2�3�1�1�-

Configuration of a digital input, impulse mode.

When selecting the configuration of digital inputs in impulse mode, you can program the

following parameters:

The input name.

The units.

The decimals.

The energy meter factor.

The configuration of a digital input in impulse mode in the expansion modules is the same as
the configuration of the digital inputs in impulse mode integrated in the unit, see

“5.6.17.2.-

Configuration of digital inputs, impulse mode.”

7�2�3�1�2�-

Configuration of a digital input, logic state mode.

When selecting the configuration of digital inputs in logic state mode, you can program the input

logic as positive or negative.

The configuration of a digital input in logic state mode in the expansion modules is the same as

the configuration of the digital inputs in logic state mode integrated in the unit, see

“5.6.17.3.-

Configuration of digital inputs, logic state mode.”

7�2�3�2�-

Relay digital outputs�

Select the output to configure on the main configuration screen of the relay digital outputs,

figure 157

.

figure 157: Main configuration screen of relay digital outputs.

The following options appear in the lower area:

218

CVM-B100 - CVM-B150

Instruction Manual