6�3�7�9�- Installation data

These parameters occupy 1 register each.

Table 40: Modbus memory map: Configuration variables (Installation data)

Installation data

Configuration variable

Address

Valid data window

Default value

Nominal Frequency

(1)

2720

5000 or 6000

5000

Number of quadrants

2722

2 or 4

4

(1)

The units of the frequency are at address 0x157F. Format of the units: Power of 10 (with sign).

6�3�7�10�- Cost of energy consumption and generation

The

Cost configuration variables occupy 2 registers each.

The

Currency configuration variables occupy 4 registers.

Table 41:Modbus memory map: Configuration variables (Energy cost)

energy cost

Configuration variable

Address

Valid data window

Default value

Cost per kWh of tariff 1 consumption

27D8-27D9

0 to 100

(1)

0

Cost per kWh of tariff 2 consumption

27DA-27DB

0 to 100

(1)

0

Cost per kWh of tariff 3 consumption

27DC-27DD

0 to 100

(1)

0

Cost per kWh of tariff 1 generation

27DE-27DF

0 to 100

(1)

0

Cost per kWh of tariff 2 generation

27E0-27E1

0 to 100

(1)

0

Cost per kWh of tariff 3 generation

27E2-27E3

0 to 100

(1)

0

Currency

27E4-27E7

7 ascii characters

EURO

(1)

The number of decimals are indicated at address

0x1586. Format of the units: Power of 10 (with sign).

Note: The 16 registers must be written and read at once (as a group), otherwise it will respond

with an error.

6�3�7�11�- CO

2

consumption and generation emissions

These parameters occupy 2 registers each.

Table 42:Modbus memory map: Configuration variables (CO

2

emissions)

C0

2

emissions

Configuration variable

Address

Valid data window

Default value

Tariff 1 consumption emissions ratio

2774-2775

0 to 100

(1)

0

Tariff 2 consumption emissions ratio

2776-2777

0 to 100

(1)

0

Tariff 3 consumption emissions ratio

2778-2779

0 to 100

(1)

0

Tariff 1 generation emissions ratio

277A-277B

0 to 100

(1)

0

Tariff 2 generation emissions ratio

277C-277D

0 to 100

(1)

0

Tariff 3 generation emissions ratio

277E-277F

0 to 100

(1)

0

(1)

The number of decimals are indicated at address

0x1585. Format of the units: Power of 10 (with sign)

.

Note: The 12 registers must be written at once (as a group), otherwise it will respond with an

error.