CIRCUTOR CVM-B Series User Manual

Page 189

Advertising
background image

Table 32: Configuration of local time

Local time parameter

Local time

Value

Local time

Value

UTC+1

0x0000

UTC-11

0x000C

UTC+2

0x0001

UTC-10

0x000D

UTC+3

0x0002

UTC-9

0x000E

UTC+4

0x0003

UTC-8

0x000F

UTC+5

0x0004

UTC-7

0x0010

UTC+6

0x0005

UTC-6

0x0011

UTC+7

0x0006

UTC-5

0x0012

UTC+8

0x0007

UTC-4

0x0013

UTC+9

0x0008

UTC-3

0x0014

UTC+10

0x0009

UTC-2

0x0015

UTC+11

0x000A

UTC-1

0x0016

UTC+12

0x000B

UTC

0x0017

6�3�7�3�- Language

This parameter occupies 1 register.

Table 33:Modbus memory map: Configuration variables (language).

Language

Configuration variable

Address

Valid data window

Default value

Unit language

2A9C

0: Spanish

1: English

2: German

3: French

4: Chinese

1

6�3�7�4�- Access key

The

Enable configuration variable occupies 1 register.

The

Value configuration variable occupies 4 registers.

Table 34: Modbus memory map: Configuration variables (Access key).

Access key

Configuration variable

Address

Valid data window

Default value

Enabled

2A97

0: Enabled

1: Disabled

1

Value

2A98-2A9B

0- 9

0x0001 0x0009

0x0007 0x0003

Note: The 5 registers must be written at once (as a group), otherwise it will respond with an

error

.

189

Instruction Manual

CVM-B100 - CVM-B150