CIRCUTOR CVM-B Series User Manual

Page 32

Advertising
background image

If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown

in the bar chart are calculated.

figure 23: Calculation of the bar chart�

The calculation formulas are:

Neutral-phase voltage and neutral voltage

L = Primary rated voltage* 0.9 H=

Primary rated voltage * 1.1

Min = L * 0.8 Max = H * 1.2

P

L

=

L + (( H - L) * 0.1) P

H

=

H - (( H - L) * 0.1)

Phase-phase voltage

L = Primary rated voltage* 0.9 * √3 H =

Primary rated voltage * 1.1 * √3

Min = L * 0.8 Max = H * 1.2

P

L

=

L + (( H - L) * 0.1) P

H

=

H - (( H - L) * 0.1)

Current

L = 0 H = Primary current

Min = 0 Max = H * 1.2

P

L

= 0

P

H

=

H - (( H - L) * 0.1)

The alarm and pre-alarm zones L are not displayed.

Power ratings

L = 0 H = Primary rated voltage * Primary current

Min = 0 Max = H * 1.2

P

L

= 0

P

H

=

H - (( H - L) * 0.1)

The alarm and pre-alarm zones L are not displayed.

frequency 50 Hz

L = 45 H = 55

Min = L * 0.95 Max = H * 1.05

P

L

=

L + (( H - L) * 0.25) P

H

=

H - (( H - L) * 0.25)

32

CVM-B100 - CVM-B150

Instruction Manual

Advertising