Vcm-x configuration, Vcm-x confi guration screens, Vcm-x / rne operator interfaces technical guide 20 – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 20

Advertising
background image

Zone

Zone

VCM-X CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

20

VCM-X Confi guration Screens

Confi guration Screen #5 - Reset Interval Rate

VCM-X Cnfg ID 59

Reset Interval

Rate...: 20 s

[1-250 Seconds]

If you selected Space or Return Air Temperature Reset in Screen #4,
enter a value in seconds between 1-250. This value determines how fast
the Supply Air Temperature Setpoint is adjusted as the Reset Source
changes. Default is 20 seconds.

Confi guration Screen #6 - Dehumidifi cation

Control

VCM-X Cnfg ID 59
Dehumidification

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if your system requires Dehumidifi cation Control.

Enter

<0>

for NO. Default is NO.

Confi guration Screen #7 - Dehumidifi cation

Priority

VCM-X Cnfg ID 59
Dehumidification

Priority: NO
[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is a Priority during the Occupied

Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter

<0>

for NO.

Confi guration Screen #8 - Dehumidifi cation

Unoccupied

VCM-X Cnfg ID 59
Dehumidification

Unoccupied: NO

[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is required during the Unoccu-

pied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter

<0>

for NO. Default is NO.

Confi guration Screen #9 - Outdoor Humidity

Sensor

VCM-X Cnfg ID 59

Outdoor Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Outdoor Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #10 - Indoor Humidity

Sensor

VCM-X Cnfg ID 59

Indoor Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Indoor Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #11 - Heat During

Dehumidify

VCM-X Cnfg ID 59

Heat During

Dehumidify: NO

[0=NO 1=YES]

Enter

<1>

for YES if your application needs to use unit heat during

Dehumidifi cation to supplement Reheat. If Reheat is not available, this
selection will allow unit heat to operate in place of Reheat. Enter

<0>

for NO. Default is NO.

Confi guration Screen #12 - Economizer

Control

VCM-X Cnfg ID 59

Economizer

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if the VCM-X is controlling the Economizer. Enter

<0>

for NO. Default is NO.