VCM-X CONFIGURATION

21

VCM-X Confi guration Screens

Confi guration Screen #13 - Proof of Flow Input

VCM-X Cnfg ID 59

Proof Of Flow

Input: NO

[0=NO 1=YES]

Enter

<1>

for YES if the unit is equipped with a Proof of Flow Switch

and it is connected to the VCM-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If any
other relays such as Heating Stages or Cooling Stages are active, they
will be deactivated when the Proof of Flow Switch input is lost. Enter

<0>

for NO. Default is NO.

Confi guration Screen #14 - Modulating Cooling/

Heating

VCM-X Cnfg ID 59

Mod Cooling: NO
Mod Heating: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is controlling Modulating Heat-

ing or Modulating Cooling or both. If your HVAC unit is going to use
a Modulating Chilled Water Valve or is equipped with a Digital Com-
pressor, you must select YES for Modulating Cooling. If your HVAC
is using a Modulating Hot Water Valve, Modulating Steam Valve, or a
SCR Controlled Electric Heater, you must select YES for Modulating
Heating. This confi guration does not apply to MODGAS using the
MODGAS Controller. Enter

<0>

for NO. Default is NO.

Confi guration Screen #15 - Modulating

Heating Output Signal

VCM-X Cnfg ID 59

Mod Heating

Output Signal.: 0

[0=0-10V 1=2-10V]

Enter

<0>

for a 0-10 VDC signal to a Modulating Heat Source such as

a Hot Water Valve or SCR Electric Heater. Enter

<1>

for a 2-10 VDC

signal to a Hot Water Valve or SCR Electric Heater. Default is 0.

Confi guration Screen #16 - Modulating

Heating Reverse Acting

VCM-X Cnfg ID 59

Mod Heating

Rev Acting: NO

[0=NO 1=YES]

Enter

<1>

for YES if the Modulating Heat Source requires 0 VDC to

open and 10 VDC to close. Enter

<0>

for NO. Default is NO.

Confi guration Screen #17 - Modulating

Heating Proportional Window

VCM-X Cnfg ID 59

Mod Heating

Prop. Window.: 10ºF

Time Period..: 5 s

The Modulating Heating Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Heating Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The Time Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulat-
ing Signal. Defaults are 10ºF and 5 seconds.

Confi guration Screen #18 - Modulating Cooling

Output Signal

VCM-X Cnfg ID 59

Mod Cooling

Output Signal: 0

[0= 0-10V 1= 2-10V]

Enter

<0>

for a 0-10 VDC signal to a Modulating Cool source such as

a Chilled Water Valve. Enter

<1>

for a 2-10 VDC signal to a Chilled

Water Valve. Default is 0.

Confi guration Screen #19 - Digital Compressor

Signal

VCM-X Cnfg ID 59

Digital Compressor

Signal 1-5V : NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with a Digital Com-

pressor. Enter

<0>

for NO. Default is NO.