RNE CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

34

RNE Confi guration Screens

Confi guration Screen #33 - Building Pressure

Modulating Control

RNE Cnfg ID 101

Building Pressure

Mod Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if Modulating Building Pressure Control is needed.

Modulating Building Pressure Control is used for a VFD Exhaust Fan or
a Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for
a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Enter

<0>

for NO if Modulating Building Pressure

Control is not needed when using a Constant Volume Exhaust Fan for
On/Off Control. Default is NO.

Confi guration Screen #34 - Building Pressure

Reverse Acting

RNE Cnfg ID 101

Building Pressure

Rev Acting: NO

[0=NO 1=YES]

Enter

<1>

for YES if Reverse Acting Building Pressure control is

needed. Reverse Acting Building Pressure Control can either be On/
Off or Modulating Control. Modulating Control is normally used for
this confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open
to increase pressure. Enter

<0>

for NO. Default is NO.

Confi guration Screen #35 - Building Pressure

Output Signal

RNE Cnfg ID 101

Building Pressure

Output Signal: 0

[0=0-10V 1=2-10V]

This Screen is used to confi gure the Building Pressure Output Signal
voltage needed for your application. You can select either a 0-10 VDC
signal (default) or enter

<1>

to make the output signal 2-10 VDC as

required by the device you are using to control the pressure. Enter

<0>

for 0-10 VDC. Default is 0.

Confi guration Screen #36 - Heat Pump Control

RNE Cnfg ID 101

Heat Pump

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is a Heat Pump. Enter

<0>

for

NO. Default is NO.

Confi guration Screen #37 - Reversing Valve

Active During Heat/Cool

RNE Cnfg ID 101

Rev. Valve Active

For: Cool

[0=Heat 1=Cool]

Enter

<0>

for Heat if your Heat Pump unit activates its Reversing Valve

during Heating operation. Enter

<1>

for Cool if your Heat Pump unit

activates its Reversing Valve during Cooling operation. Default is Heat.

Confi guration Screen #38 - Emergency

Shutdown Input

RNE Cnfg ID 101

Emergency Shutdown

Input: NO

[0=NO 1=YES]

Enter

<1>

for YES if a Smoke Detector/Firestat or other Emergency

Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter

<0>

for NO. Default is NO.

Confi guration Screen #39 - Return Air Bypass

Control

RNE Cnfg ID 101

Return Air Bypass Con-

trol: NO

[0=NO 1=YES]

Enter

<1>

for YES if your HVAC unit requires Return Air Bypass

Control for Dehumidifi cation Reheat. Enter

<0>

for NO. Default is NO.