RNE CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

30

RNE Confi guration Screens

Confi guration Screen #5 - Reset Interval Rate

RNE Cnfg ID 101

Reset Interval

Rate...: 20 s

[1-250 Seconds]

If you selected Space or Return Air Temperature Reset in Screen #4,
enter a value in seconds between 1-250. This value determines how fast
the Supply Air Temperature Setpoint is adjusted as the Reset Source
changes. Default is 20 seconds.

Confi guration Screen #6 - Dehumidifi cation

Control

RNE Cnfg ID 101

Dehumidification

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if your system requires Dehumidifi cation Control.

Enter

<0>

for NO. Default is NO.

Confi guration Screen #7 - Dehumidifi cation

Priority

RNE Cnfg ID 101

Dehumidification

Priority: NO
[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is a Priority during the Occupied

Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter

<0>

for NO.

Confi guration Screen #8 - Dehumidifi cation

Unoccupied

RNE Cnfg ID 101

Dehumidification

Unoccupied: NO

[0=NO 1=YES]

Enter

<1>

for YES if Dehumidifi cation is required during the Unoccu-

pied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter

<0>

for NO. Default is NO.

Confi guration Screen #9 - Outdoor Humidity

Sensor

RNE Cnfg ID 101

Outdoor Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Outdoor Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #10 - Indoor Humidity

Sensor

RNE Cnfg ID 101

Indoor Humidity

Sensor: NO

[0=NO 1=YES]

Enter

<1>

for YES if the HVAC unit is equipped with an Indoor Air

Humidity Sensor. Enter

<0>

for NO. Default is NO.

Confi guration Screen #11 - Heat During

Dehumidify

RNE Cnfg ID 101

Heat During

Dehumidify: NO

[0=NO 1=YES]

Enter

<1>

for YES if your application needs to use unit heat during

Dehumidifi cation to supplement Reheat. If Reheat is not available, this
selection will allow unit heat to operate in place of Reheat. Enter

<0>

for NO. Default is NO.

Confi guration Screen #12 - Economizer

Control

RNE Cnfg ID 101

Economizer

Control: NO

[0=NO 1=YES]

Enter

<1>

for YES if the RNE is controlling the Economizer. Enter

<0>

for NO. Default is NO.