VCM-X CONFIGURATION

25

VCM-X Confi guration Screens

Confi guration Screen #39 - Emergency

Shutdown Input

VCM-X Cnfg ID 59

Emergency Shutdown

Input: NO

[0=NO 1=YES]

Enter

<1>

for YES if a Smoke Detector/Firestat or other Emergency

Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter

<0>

for NO. Default is NO.

Confi guration Screen #40 - Return Air Bypass

Control

VCM-X Cnfg ID 59

Return Air Bypass Con-

trol: NO

[0=NO 1=YES]

Enter

<1>

for YES if your HVAC unit requires Return Air Bypass

Control for Dehumidifi cation Reheat. Enter

<0>

for NO. Default is NO.

Confi guration Screen #41 - Broadcast OA Temp

VCM-X Cnfg ID 59

Broadcast Outdoor

Temperature: NO

[0=NO 1=YES]

The VCM-X can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in
order for this feature to operate. Enter

<1>

for YES - Broadcast Outdoor

Temperature. Enter

<0>

for NO. Default is NO.

Confi guration Screen #42 - Broadcast OA Humidity

VCM-X Cnfg ID 59

Broadcast Outdoor

Humidity: NO
[0=NO 1=YES]

The VCM-X can broadcast its Outdoor Air Humidity reading to other
HVAC units if they are not equipped with their own Outdoor Air Hu-
midity sensors. A network communications device is required in order
for this feature to operate. Enter

<1>

for YES - Broadcast Outdoor

Humidity. Enter

<0>

for NO. Default is NO.

Confi guration Screen #43 - Broadcast Supply

Temperature

VCM-X Cnfg ID 59

Broadcast Supply

Temperature: YES

[0=NO 1=YES]

This broadcast sends the VCM-X’s Supply Air Temperature to all con-
trollers on its local loop. This broadcast needs to be confi gured on a VAV
or Zoning System using the VCM-X with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature
to operate. Enter

<1>

for YES or

<0>

to NO. Default is NO.

Confi guration Screen #44 - Broadcast Status

Fan & Heat

VCM-X Cnfg ID 59

Broadcast Status

Fan & Heat: NO

[0=NO 1=YES]

This broadcast sends the VCM-X’s Supply Fan and Heating Status to
all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for
this feature to operate. Enter

<1>

for YES or

<0>

for NO. Default is NO.

Confi guration Screen #45 - Broadcast Internal

Time Clock

VCM-X Cnfg ID 59

Broadcast Internal

Time Clock: NO

[0=NO 1=YES]

This broadcast sends the time from the VCM-X’s Internal Time Clock
to all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
controllers. A network communications device is required in order for
this feature to operate, but can also be used to synchronize all controllers
on the local loop. Enter

<1>

for YES or

<0>

for NO. Default is NO.