VCM-X / RNE Operator Interfaces Technical Guide

VCM-X / RNE SETPOINTS

43

Setpoint Screen #19 - Outdoor Air CFM Control

VCM-X / RNE Spts

OA CFM CONTROL

Min CFM.: 0.10 K
Max CFM.: 0.10 K

If controlling the Outdoor Air Damper to a CFM setpoint, this screen
allows you to set the design Minimum and Maximum required Outdoor
Airfl ow CFM values for the Air Handler. The OA Max CFM limits the
damper operation during CO

2

override conditions. K = 1000

Description

Minimum

Default

Maximum

OA Minimum CFM

0.10 K

.10 K

200 K

OA Maximum CFM

0.10 K

.10 K

200 K

Setpoint Screen #20 - Outdoor Air CFM

Deadband

VCM-X / RNE Spts

OA CFM CONTROL

OA CFM DB...: 10CFM

The is the deadband above and below the OA CFM Control Setpoint
which helps prevent hunting.

Description

Minimum

Default

Maximum

OA CFM Deadband

0 CFM

10 CFM

20,000 CFM

Setpoint Screen #21 - Economizer Maximum

Position if High CO

2

Level

VCM-X / RNE Spts

Maximum Economizer

Position if High CO2
Level Occurs.: 100%

This Setpoint allows you to set the Maximum Position the Economizer
will open if high CO

2

conditions occur in the space. The Maximum

Economizer Position Setpoint is used to limit the amount of Outdoor Air
that will be introduced to the HVAC unit in order to ensure the unit is
operating within its Heating and Cooling design limitations. As shown
in the table below, the Minimum setting for this Setpoint is the value
previously set for the Economizer Min Position Setpoint.

Description

Minimum

Default

Maximum

Maximum Economizer

Position If High CO

2

Level Occurs

Economizer

Minimum

Position

100%

100%

VCM-X / RNE Setpoint Screens

Setpoint Screen #17 - Economizer OAT/WB

Enable

VCM-X / RNE Spts

Economizer Setpoints

OAT/WB Enable: 55ºF

If an Outdoor Air Humidity Sensor is not connected to the VCM-X or
RNE and the Outdoor Air Temperature falls below this Setpoint, the
Economizer can be used for Free Cooling. If an Outdoor Air Humidity
Sensor is connected to the VCM-X or RNE, then a Wetbulb Temperature
will be calculated and used instead of the Outdoor Air Drybulb Tem-
perature to determine when Free Cooling can be used.

Description

Minimum

Default

Maximum

Economizer Setpoints

OAT/WB Enable

0ºF

55ºF

80ºF

Setpoint Screen #18 - Economizer Minimum

Position & Control Rate

VCM-X / RNE Spts

Economizer Setpoints

Min Position.: 10 %

Control Rate.: 90

The Economizer (OA Damper) Min Position Setpoint is maintained
during the Occupied Mode even if the Economizer is disabled due to the
OA Temperature or Wetbulb Temperature being above the Economizer
Enable Setpoint. The Control Rate Setpoint allows you to adjust the
Economizer to modulate the OA Damper Actuator faster or slower as
desired. The Control Rate Setpoint range is 10-99. Larger numbers make
the Economizer Outdoor Air Damper Actuator modulate faster, smaller
numbers make the Outdoor Air Damper Actuator modulate slower.

Description

Minimum

Default

Maximum

Economizer Min Position

0%

10%

100%

Economizer Control Rate

10

90

99

Revised: 9/14/12