RNE CONFIGURATION

33

RNE Confi guration Screens

Confi guration Screen #27 - Monitor Return Air

CFM

RNE Cnfg ID 101

Monitor Return

Air CFM: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have an airfl ow monitoring station measuring

the CFM of the return airfl ow stream of this unit. Enter

<0>

for NO.

Default is NO.

Confi guration Screen #28 - Return Duct/

Damper Size

RNE Cnfg ID 101

Return Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the return air CFM, you need to
enter the area in square feet of the return air duct/damper. When measur-
ing the return air damper area, be sure to measure the inside dimensions
of the damper. The more accurate the measurements, the more accurate
the CFM reading will be. This value needs to be accurate to 2 decimal
places. Default is 0.00.

Confi guration Screen #29 - Monitor Supply Air

CFM

RNE Cnfg ID 101

Monitor Supply

Air CFM: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have an airfl ow monitoring station measuring

the CFM of the supply airfl ow stream of this unit. Enter

<0>

for NO.

Default is NO.

Confi guration Screen #30 - Supply Duct/

Damper Size

RNE Cnfg ID 101

Supply Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the supply air CFM, you need
to enter the area in square feet of the supply air duct/damper. When
measuring the supply duct damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.

Confi guration Screen #31 - CO

2

Sensor

Output Signal

RNE Cnfg ID 101

CO2 Sensor

Output Signal: 0

[0=None 1=mA 2=VDC]

The RNE needs to know what type of CO

2

sensor signal output is being

provided. Enter

<2>

for a 0-10 VDC CO

2

sensor signal (standard sensor

used). Enter

<1>

for a 4-20 mA CO

2

sensor signal. Enter

<0>

if no CO

2

sensor is used. Default is None.

Confi guration Screen #32 - CO

2

Sensor

Maximum Scale

RNE Cnfg ID 101

CO2 Sensor Maximum

Scale: 2000 PPM

Enter 0 If No Sensor

Default is 2000 PPM. The RNE needs to know the CO

2

Sensor scaling

for proper reading of the CO

2

Sensor output. The Standard CO

2

Sensor

should be scaled to 2000 PPM. Enter

<0>

if no CO

2

sensor is used.

Default is 2000.