RNE CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

36

Confi guration Screen #46 - Broadcast VAV

Boxes Force to Max

RNE Cnfg ID 101

Broadcast VAV Boxes

Force To Max: YES

[0=NO 1=YES]

This broadcast is to ensure the VAV/Zone Controllers will drive their
dampers to the Max Airfl ow Damper Position during Morning Warm-
up. This is important to allow the proper amount of airfl ow for Heating
in the HVAC unit. Enter

<1>

for YES or

<0>

for NO. Default is YES.

Confi guration Screen #47 - Broadcast VAV

Boxes Force to Fixed

RNE Cnfg ID 101

Broadcast VAV Boxes

Force To Fixed: NO

[0=NO 1=YES]

Enter

<1>

for YES to have all VAV/Zone Controllers connected to this

RNE Controller forced to their “Fixed Airfl ow” Position during the
Morning Warm-up Mode of operation. Enter

<0>

for YES if you do

not want this to occur. See the VAV/Zone Controller Setpoint Screens
for setting of the “Fixed Airfl ow” position. Default is NO.

Confi guration Screen #48 - 1 HVAC Unit with

Boxes on Multiple Loops

RNE Cnfg ID 101

1 HVAC Unit w/ Boxes

On Multi. Loops: NO

[0=NO 1=YES]

Enter

<1>

for YES to have all broadcasts that have been confi gured on

Confi guration Screens 42 through 47 sent to all local loops on the entire
system, not just the local loop the RNE Controller is on. This is normally
only required if you have a large HVAC unit that requires more than
the 58 VAV/Zone Controllers normally allowed on the local loop. This
allows other VAV/Zone Controllers connected on additional local loops
to receive the required broadcasts. This only is allowed when you have
a single RNE Controller with VAV/Zone Controllers on multiple loops.
Other RNE or add-on devices may be connected but no other RNE with
VAV/Zone Controllers can be connected on the system. Enter

<0>

for

NO. Default is NO.

Confi guration Screen #49 - Uses R410A

Refrigerant

RNE Cnfg ID 101

Unit Uses R410A
Refrigerant: NO

[0=NO 1=YES]

Enter

<1>

for YES if your HVAC unit uses R410A Refrigerant. Enter

<0>

for NO. Default is 1.

Confi guration Screen #50 - Main Fan

Maximum Voltage

RNE Cnfg ID 101

Max Main Fan Aout

Voltage: XX.X VDC

Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum
output voltage. The Static Pressure and Output % Status Screen will
display 0% to 100%, but the output will range from 0 VDC to the value
set in this screen. Default is 0 VDC.