VAV/ZONE CONTROLLER PROGRAMMING

VCM-X / RNE Operator Interfaces Technical Guide

63

VAV/Zone Setpoint Screens

Setpoint Screen #16 - Push-Button Override

Duration

XX Box Spts IDXXXX

Push-Button Override
Duration : X.X Hr

If the Flush Mount Wall Sensor has the optional Push-Button Over-
ride, this is the amount of the VAV/Zone Controller will resume using
its Occupied Setpoints during unoccupied mode. This will generate a
call for the Air Handler to start its fan and provide heating or cooling,
depending on how you confi gure the Air Handler.

Description

Minimum

Default

Maximum

Duration

0.0 Hr

0.0 Hr

8.0 Hr

Setpoint Screen #17 - Maximum EMS Offset

XX Box Spts IDXXXX

Maximum EMS Setpoint

Offset...: XXºF

If the Energy Management System (EMS) is activated, the heat and cool
setpoints can be spread apart by this amount.

Description

Minimum

Default

Maximum

Maximum EMS Setpoint

Offset

0ºF

0ºF

30ºF

Setpoint Screen #18 - Sensor Calibration for

Space Temp and Supply Air Temp

Sensor Calibration

SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº

[SAT Only if Sensor]

The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.

NOTE: The Supply Air Temperature calibration offset only oper-

ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.

Description

Minimum

Default

Maximum

SPC (Space Temp)

-100ºF

0ºF

+100ºF

SAT (Supply Air)

-100ºF

0ºF

+100ºF