VCM-X / RNE SETPOINTS

VCM-X / RNE Operator Interfaces Technical Guide

42

Setpoint Screen #13 - Dehumidifi cation Indoor

RH & OA Dewpoint

VCM-X / RNE Spts

Dehumidification Spt

Indoor RH....: 50%

OA Dewpoint..: 55ºF

On VAV or CAV confi gured units that are not using 100% Outdoor Air,
when the Indoor Relative Humidity percentage rises above the Indoor
RH Setpoint, the unit will start operating in Dehumidifi cation Mode.

If an Indoor Humidity Sensor is installed, the unit will reset the Coil
Suction Temperature Setpoint as needed to maintain this Indoor RH
Setpoint. This includes VAV, CAV and MUA applications.

On MUA confi gured units that are using 100% Outdoor Air, when the
Outdoor Air Dewpoint Temperature rises above the OA Dewpoint Set-
point, the unit will start operating in Dehumidifi cation Mode.

Description

Minimum

Default

Maximum

Dehumidifi cation Setpoint

Indoor RH

1%

50%

100%

Dehumidifi cation Setpoint

OA Dewpoint

35ºF

55ºF

80ºF

Setpoint Screen #14 - Dehumidifi cation Coil

Temperature

VCM-X / RNE Spts
Dehumidification
Coil Temperature

Setpoint.....: 45ºF

During the Dehumidifi cation Mode, the VCM-X / RNE uses the calcu-
lated Coil Temperature to activate DX Cooling based on this Dehumidi-
fi cation Coil Temperature Setpoint. The VCM-X / RNE uses a Suction
Pressure Transducer to read Suction Pressure (the Saturation Vapor
Pressure of the Refrigerant) and converts this Suction Pressure reading
to a Coil Temperature value. This calculation is based on using R22 or
R410A refrigerant only and will not work with any other refrigerant.
This setpoint determines the number of compressor stages that need to
be activated to maintain the Dehumidifi cation Coil Temperature Setpoint.

Description

Minimum

Default

Maximum

Dehumidifi cation Coil
Temperature Setpoint

35ºF

45ºF

70ºF

VCM-X / RNE Setpoint Screens

Setpoint Screen #15 - Cooling Head Pressure

Setpoint

VCM-X / RNE Spts

Cooling

Head Pressure

Setpoint: 315PSI

If you are using the Head Pressure Module, this is the Cooling Setpoint
for control of the condenser fan speed. This is based on the highest
head pressure reading of up to 4 Head Pressure Sensors. This screen
only applies if using the VCM-X Modular, VCM-X WSHP Controller,
or RNE Controller.

See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide
for detailed information.

Description

Minimum

Default

Maximum

Cooling Head Pressure

Setpoint

200 PSI

315 PSI

400 PSI

Setpoint Screen #16 - Reheat Head Pressure

Setpoint

VCM-X / RNE Spts

Reheat

Head Pressure

Setpoint: 400PSI

If you are using the Head Pressure Module, this is the Reheat Setpoint
for control of the condenser fan speed during dehumidifi cation. This is
based on the highest head pressure reading of up to 4 Head Pressure
Sensors. This screen only applies if using the VCM-X Modular, VCM-X
WSHP Controller, or RNE Controller.

See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide
for detailed information.

Description

Minimum

Default

Maximum

Reheat Head Pressure

Setpoint

200 PSI

400 PSI

400 PSI