Vcm-x / rne setpoints, Vcm-x / rne setpoint screens, Vcm-x / rne operator interfaces technical guide 40 – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 40

Advertising
background image

VCM-X / RNE SETPOINTS

VCM-X / RNE Operator Interfaces Technical Guide

40

Setpoint Screen #7 - Heat Reset Source

VCM-X / RNE Spts

Heat Rst Source Spts

SpcHi: 70 SAT: 120º
SpcLo: 70 RST: 120º

If no Reset Source has been confi gured in Confi guration Screen #4,
then this screen will read Heat Rst Not Confi g and will not be used. If
a Reset Source has been confi gured in Confi guration Screen #6, then
the names of the values on the left side of this screen will correspond to
the Reset Source that was confi gured. This screen will then allow you
to input the upper and lower limits for the range of values of the Reset
Source on the left side of the screen and will show the corresponding
Heating Supply Air SAT and Rst Limit values that you entered on the
previous screen. Single Zone VAV Reset of the Supply Fan VFD is ad-
dressed in the last paragraph.

Please note that the SAT and Rst Limit values on the right side of this
screen cannot be changed on this screen; they are simply displayed from
what was entered on the Setpoint Screen #6. For each line, the value on
the left corresponds to the value on the right. So if the Space Temperature
Sensor has been confi gured as the Reset Source, then when the Space
Temperature is at or above the SpcHi Temperature Setpoint, the Supply
Air Heating Setpoint will be reset to its lowest value, the SAT Setpoint.
If the Space Temperature is at or below the SpcLo Setpoint, the Supply
Air Heating Setpoint will be reset to its highest value, the Heating Rst
Limit. Then, as the Space Temperature moves from its low value to its
high value, the Supply Air Heating Setpoint will be proportionally reset
from its high value to its low value.

Depending on whether reset has been confi gured or not, the options for
the names of the values on the left side of the screen are SpcHi, SpcLo,
OatHi, OatLo, RatHi, RatLo, VLT, VFD, NoRST.

In the examples that follow, the desired Space Temperature in
Heating Mode is 71ºF:

Space Temperature Heat Reset:
Space Temperature (SPC Hi) = 71ºF SAT Setpoint (SAT) = 90ºF
Space Temperature (SPC Lo) = 70ºF SAT Setpoint (Rst) = 120ºF

VFD Percentage Heat Reset:
VFD Percentage (VFD) = 30% SAT Setpoint (SAT) = 90ºF
VFD Percentage (VFD) = 70% SAT Setpoint (Rst) = 120ºF

Input Voltage Heat Reset:
Input Voltage (VLT) = 0 Volts SAT Setpoint (SAT) = 90ºF
Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 120ºF

In the Heating Mode in a Single Zone VAV application, the Supply Fan
VFD speed will proportionally modulate as the Space Temperature falls
within the range set on this screen. Upon entering the Heating Mode, the
fan will start at 50% and modulate up to 100% as the Space Temperature
falls from the SpcHi Setpoint to the SpcLo Setpoint. The SpcHi Set-
point should be the same as the Space Heating Setpoint (Mode Enable
Setpoint) from Setpoint Screen #1. The SAT and RST Setpoints on the
right side of the screen are not used.

In the examples that follow, the desired Space Temperature in
Cooling Mode is 75ºF:

Space Temperature Cool Reset:
Space Temperature (SPC Hi) = 75ºF SAT Setpoint (SAT) = 55ºF
Space Temperature (SPC Lo) = 74ºF SAT Setpoint (Rst) = 65ºF

VFD Percentage Cool Reset:
VFD Percentage (VFD) = 70% SAT Setpoint (SAT) = 55ºF
VFD Percentage (VFD) = 30% SAT Setpoint (Rst) = 65ºF

Input Voltage Cool Reset:
Input Voltage (VLT) = 0 Volts SAT Setpoint (SAT) = 55ºF
Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 65ºF

In the Cooling Mode in a Single Zone VAV application, the Supply Fan
VFD speed will proportionally modulate as the Space Temperature rises
within the range set on this screen. Upon entering the Cooling Mode, the
fan will start at 30% and modulate up to 100% as the Space Temperature
rises from the SpcLo Setpoint to the SpcHi Setpoint. The SpcLo Set-
point should be the same as the Space Cooling Setpoint (Mode Enable
Setpoint) from Setpoint Screen #1. The SAT and RST Setpoints on the
right side of the screen are not used.

Setpoint Screen #6 - SAT Heating Setpoints

If no Reset Source has been confi gured in Confi guration Screen #4, then
this setpoint will be the Supply Air Temperature Heating Setpoint. Line
4 will be blank. If a Reset Source has been confi gured in Confi guration
Screen #4, then Line 4 will read Rst Limit. Reset is always upward from
the SAT setpoint to the Reset Limit setpoint. So, the SAT will be the
lowest temperature the Supply Air Setpoint can be reset to and Reset
Limit will be the highest temperature the Supply Air Setpoint can be
reset to. The Heating Supply Air Temperature Setpoint will automati-
cally be reset warmer or colder within this range as the Reset Source
(next screen) moves within its range.

VCM-X / RNE Spts
SAT Heating Spts

Heating..: 120ºF
Rst Limit: 120ºF

Description

Minimum

Default

Maximum

SAT Heating Spt

40ºF

120ºF

200ºF

Reset Limit Spt

40ºF

120ºF

200ºF

VCM-X / RNE Setpoint Screens

Advertising
This manual is related to the following products: