VCM-X / RNE SETPOINTS

47

Setpoint Screen #36 - Heat Wheel Defrost

VCM-X / RNE Spts

Heat Wheel Defrost

Setpoint: 30ºF

The unit will go into Heat Wheel Defrost Mode when the Outdoor Air
is below this setpoint.

Description

Minimum

Default

Maximum

Heat Wheel Defrost

0ºF

30ºF

50ºF

Setpoint Screen #37 - Internal Schedule

Optimal Start Soak Multiplier

VCM-X / RNE Spts

Internal Schedule

Optimal Start Soak

Multiplier: 0.0

The Internal Schedule Optimal Start Soak Multiplier Setpoint is a multi-
plier that if set to a number greater than 0 will be used as a multiplier for
calculating the Optimal Start Time for the HVAC unit. This multiplier
is only applied if the unit has been off for more than 24 hours. See the
VCM-X Controller Technical Guide, VCM-X Modular E-BUS Controller
Technical Guide,
or RNE Controller Technical Guide for more detailed
information regarding the Optimal Start. This multiplier is only applied
if you are using the VCM-X / RNE Internal Schedule.

Description

Minimum

Default

Maximum

Internal Schedule Optimal

Start Soak Multiplier

0.0

0.0

5.0

Setpoint Screen #38 - Trend Log Interval

VCM-X / RNE Spts

Trend Log

Interval: 15 MIN

An internal Trend Log is constantly updated at a rate equal to this value.

Description

Minimum

Default

Maximum

Trend Log Interval

1 Min

15 Min

60 Min

VCM-X / RNE Setpoint Screens

Setpoint Screen #39 - Sensor Calibration for

SPC & SAT

VCM-X / RNE Spts

Sensor Calibration

SPC: XX.Xº 0.00º
SAT: XX.Xº 0.00º

If the Space or Supply Air Temperature Sensors are reading incorrectly,
you can use this option to enter an offset temperature to adjust the Sen-
sor’s Temperature. Enter a positive Sensor Calibration value to raise the
Space Temperature and/or Supply Air Temperature Sensor reading and
a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration SPC

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration SAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #40 - Sensor Calibration for

RAT & OAT

VCM-X / RNE Spts

Sensor Calibration

RAT: XX.Xº 0.00º
OAT: XX.Xº 0.00º

If the Return Air or Outdoor Air Temperature Sensors are reading incor-
rectly, you can use this option to enter an offset temperature to adjust
the Sensor’s Temperature. Enter a positive Sensor Calibration value to
raise the Return Air Temperature and/or Outdoor Air Temperature Sensor
reading and a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration RAT

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration OAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #41 - Sensor Calibration for

COIL

VCM-X / RNE Spts

Sensor Calibration

COIL: XX.Xº 0.00º

If the Coil Temperature reading is too high, enter a negative calibration
offset to decrease the reading. If it is too low, enter a positive value to
increase the reading.

Description

Minimum

Default

Maximum

Sensor Calibration COIL

-30.0ºF

0.0ºF

+30.0ºF