VCM-X / RNE STATUS

VCM-X / RNE Operator Interfaces Technical Guide

56

VCM-X / RNE Status Screens

Line 2-3 Current Head Pressure Cooling or Reheat Setpoint

If you are using the VCM-X Modular, VCM-X WSHP,

or RNE Controller and have a One Condenser or Two

Condenser Head Pressure Module attached to the unit,

the Head Pressure Cooling or Reheat Setpoint will display,

depending on what mode the Module is in. This status

value will show 0 if not in the Cooling or Dehumidifi cation

Mode.

Status Screen 23 - Head Pressure Condenser

Fan #1

VCMX-M/HP Cnfg ID 102

Cond. Fan Sect. #1
Head Pr.....: 0PSI
Cond Fan Spd: 0%

Line 2 Condenser Fan #1

If you are using the VCM-X Modular, VCM-X WSHP, or

RNE Controller and have a One Condenser or Two

Condenser Head Pressure Module attached to the unit, this

line displays Condenser Fan #1.

Line 3 Head Pressure

This line indicates the highest of up to 4 current Head

Pressure readings on a One Condenser Head Pressure

Module. If using a Two Condenser Head Pressure Module,

this line indicates the highest of the fi rst 2 current Head

Pressure readings on that module.

Line 4 Condenser Fan Speed

This line displays the speed of the associated Condenser

Fan (0-100%) that is currently necessary to maintain the

Head

Pressure

Setpoint.

Status Screen 24 - Head Pressure Condenser

Fan #2

VCMX-M/HP Cnfg ID 102

Cond. Fan Sect. #2
Head Pr.....: 0PSI
Cond Fan Spd: 0%

Line 2 Condenser Fan #2

If you are using the VCM-X Modular, VCM-X WSHP,

or RNE Controller and have a Two Condenser Head

Pressure Module attached to the unit, this line displays

Condenser

Fan

#2.

Line 3 Head Pressure

This line indicates the highest of the second two Head

Pressure readings of the Two Condenser Head Pressure

Module.

Line 4 Condenser Fan Speed

This line displays the speed of the associated Condenser

Fan (0-100%) that is currently necessary to maintain the

Head

Pressure

Setpoint.

Status Screen 25 - Return Air Damper Signal

& Bypass Damper Signal

VCM-X / RNE v1.00

Return Dmp..: XXX%
Bypass Dmp..: XXX%

[Optional Outputs]

Line 2 Current Return Air Damper Signal

Indicates the current Output Signal percentage being sent to

the Return Air Damper Actuator. If you haven’t confi gured

a Return Air Bypass Damper, [No Return Dmp Confg] will

be displayed instead.

Line 3 Current Return Air Bypass Damper Signal

Indicates the current Output Signal percentage being sent to

the Return Air Bypass Damper Actuator. If you haven’t

confi gured a Return Air Bypass Damper, [No Bypass Dmp

Confg] will be displayed instead.

Line 4 Indicates That These Are Optional Outputs

This output may or may not have live data to display.

Status Screen 22 - Head Pressure Setpoint

VCMX-M/HP Cnfg ID 102

Current

Head Pr Spt: 0 PSI