Vcm-x configuration, Vcm-x confi guration screens, Vcm-x / rne operator interfaces technical guide 22 – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 22

Advertising
background image

Zone

Zone

VCM-X CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

22

VCM-X Confi guration Screens

Confi guration Screen #20 - Modulating Cooling

Reverse Acting

VCM-X Cnfg ID 59

Mod Cooling

Rev Acting: NO

[0=NO 1=YES]

Enter

<1>

for YES if the Modulating Cooling Source requires 0 VDC

to open and 10 VDC to close. You cannot use a Reverse Acting Signal if
a Digital Compressor is being used. Enter

<0>

for NO. Default is NO.

Confi guration Screen #21 - Modulating Cooling

Proportional Window

VCM-X Cnfg ID 59
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s

The Modulating Cooling Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The Time Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulat-
ing Signal. Defaults are 10ºF and 30 seconds.

Confi guration Screen #22 - Head Pressure

Module Installed

VCMX-M/HP Cnfg ID 102

Head Pressure

Module Installed: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have a Head Pressure Module installed. Enter

<0>

for NO. This screen only applies if using the VCM-X Modular or

WSHP Controller. Default is NO.

Confi guration Screen #23 - Full Digital Module/

WSHP w/Multiple Digital Scroll

Compressors OR Dual Digital Module/WSHP

w/2 Digital Scroll Compressors Installed

VCMX-M/HP Cnfg ID 102

Full Digital Module

Installed: NO

[0=NO 1=YES]

If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A) is being
used, this screen will appear. Enter

<1>

for YES if you have either a

Full Digital Module installed or if you have a Water Source Heat Pump
Module installed and in both cases all the compressors in the unit are
Digital Scroll Compressors (2 Digital Compressors only or all 4 Digital
Compressors). If you have a combination of Digital Compressors and
Fixed Compressors, enter

<0>

for NO.

VCMX-M/HP Cnfg ID 102

Dual Digital Module

Installed: NO

[0=NO 1=YES]

If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-C) is being used,
this screen will appear. Enter

<1>

for YES if you have a Dual Digital

Module installed or if the VCM-X WSHP Controller has two Digital
Scroll Compressors. Enter

<0>

for NO.

Confi guration Screen #24 - Split Condenser

VCMX-M/HP Cnfg ID 102

Is this a

Split Condenser: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have a Split Condenser with two physically

separate condenser sections. This requires a Two Condenser Head Pres-
sure Module. Enter

<0>

for NO. This screen only applies if using the

VCM-X or WSHP Modular Controller. Default is NO.