VCM-X / RNE Operator Interfaces Technical Guide

RNE CONFIGURATION

35

Confi guration Screen #40 - Broadcast OA Temp

RNE Cnfg ID 101

Broadcast Outdoor

Temperature: NO

[0=NO 1=YES]

The RNE can broadcast its Outdoor Air Temperature Reading to other
HVAC units if they are not equipped with their own Outdoor Air Tem-
perature sensors. A network communications device is needed in order
for this feature to operate. Enter

<1>

for YES - Broadcast Outdoor

Temperature. Enter

<0>

for NO. Default is NO.

Confi guration Screen #41 - Broadcast OA Humidity

RNE Cnfg ID 101

Broadcast Outdoor

Humidity: NO
[0=NO 1=YES]

The RNE can broadcast its Outdoor Air Humidity reading to other HVAC
units if they are not equipped with their own Outdoor Air Humidity
sensors. A network communications device is required in order for this
feature to operate. Enter

<1>

for YES - Broadcast Outdoor Humidity.

Enter

<0>

for NO. Default is NO.

Confi guration Screen #42 - Broadcast Supply

Temperature

RNE Cnfg ID 101

Broadcast Supply

Temperature: YES

[0=NO 1=YES]

This broadcast sends the RNE’s Supply Air Temperature to all Control-
lers on its local loop. This broadcast needs to be confi gured on a VAV
or Zoning System using the RNE with Orion VAV/Zone Controllers. A
network communications device is required in order for this feature to
operate. Enter

<1>

for YES or

<0>

to NO. Default is NO.

Confi guration Screen #43 - Broadcast Status

Fan & Heat

RNE Cnfg ID 101

Broadcast Status

Fan & Heat: NO

[0=NO 1=YES]

This broadcast sends the RNE’s Supply Fan and Heating Status to all
Controllers on its local loop. This broadcast needs to be confi gured on
a VAV or Zoning System using the RNE with Orion VAV/Zone Con-
trollers. A network communications device is required in order for this
feature to operate. Enter

<1>

for YES or

<0>

for NO. Default is NO.

Confi guration Screen #44 - Broadcast Internal

Time Clock

RNE Cnfg ID 101

Broadcast Internal

Time Clock: NO

[0=NO 1=YES]

This broadcast sends the time from the RNE’s Internal Time Clock to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate, but can also be used to synchronize all Controllers on the local
loop. Enter

<1>

for YES or

<0>

for NO. Default is NO.

Confi guration Screen #45 - Broadcast Internal

Schedule

RNE Cnfg ID 101

Broadcast Internal

Schedule: NO

[0=NO 1=YES]

This is always required when you have VAV/Zone Controllers connected
to this RNE Controller. This will broadcast the Occupied and Unoccupied
Condition of the RNE Controller to all VAV/Zone Controllers on the
local loop. Enter

<1>

for YES or

<0>

for NO. Default is NO.