VCM-X / RNE STATUS

VCM-X / RNE Operator Interfaces Technical Guide

49

VCM-X / RNE Status Screens

Status

The VCM-X / RNE Controller Status Screens are accessed by pressing
the

<STATUS>

button on either the System Manager or the Modular

Service Tool. Following are the available status screens and a descrip-
tion of their functions:

Status Screen 1 - Mode

VCM-X / RNE v1.00

Occupied Mode

Vent Mode

02/15/10 05:00 PM

Line 2 Displays one of the following:

Unoccupied Mode Remote FRC Occupied

Occupied

Mode Override

Mode

Holiday

Mode

Zone

Demand!

Forced Schedule Mode OUTPUT FORCE MODE!

SUPPLY AIR CUTOFF! High CO2 Level Mode!

Line 3

If you selected Supply Air as the controlling sensor,

this line will display:

Supply Air Control

If you select Space Temp or Return Air Control, the

display will show one of the following:

Off Mode Dehumid. Mode

Defrost Mode

Vent Mode Cool Dehumid. Mode

Cool Mode Heat Dehumid. Mode

Heat Mode Warm Up Mode

Line 4

Displays one of the following:

MM/DD/YY HH:MM XX (XX = AM or PM)

Fan Starting Delay and then time will display

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2 - Cooling, Heating, Economizer

VCM-X / RNE v1.00

Cooling Enabled
Heating Enabled

Economizer Disabled

Line 2

Displays one of the following:

Cooling

Enabled

Cooling

Disabled

Line 3

Displays one of the following:

Heating

Enabled

Heating

Disabled

Line 4

Displays one of the following:

Economizer Enabled

Economizer

Disabled

Status Screen 3 - Mode Enable Temperature &

Mode Cooling and Heating Setpoints

VCM-X / RNE v1.00

Enable Tmp.: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF

Line 2 Mode Enable Temperature

Can be the Supply Air Temperature, Return Air

Temperature, Outdoor Air Temperature, or Space

Temperature, depending on which one has been

confi gured as the Mode Enable Sensor.

Line 3

Cooling Mode Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.

Line 4

Heating Mode Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.

Status Screen 4 - Supply Air Temperature &

Setpoint

VCM-X / RNE v1.00

Supply Air.: XX.XºF
Supply Spt.: XX.XºF

Line 2 Current Supply Air Temperature

The Supply Air Temperature is always required. If a

Supply Air Temperature Sensor is not installed, the VCM-X

/ RNE Controller will not operate correctly and will display

0°F.

Line 3

Current Active Supply Air Setpoint

This is the Supply Air Setpoint for the mode that the

unit is currently operating in. If the Supply Air Reset is

confi gured, this is the calculated setpoint based on the

current Reset Source conditions.