Vcm-x / rne setpoints, Vcm-x / rne setpoint screens, Vcm-x / rne operator interfaces technical guide – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 45

Advertising
background image

VCM-X / RNE Operator Interfaces Technical Guide

VCM-X / RNE SETPOINTS

45

Decreasing this percentage decreases the airfl ow through the Return
Air Bypass Damper by causing the Return Air Damper to move further
towards its open position in relation to the Return Air Bypass Damper
moving towards its closed position.

Description

Minimum

Default

Maximum

Return Air Bypass

Damper Factor

0%

40%

100%

Setpoint Screen #26 - Supply Fan Starting

Delay Timer

VCM-X / RNE Spts

Fan Starting Delay

Timer...: 255 s

This is the Supply Fan Starting Delay Timer initiated whenever the
VCM-X / RNE initiates Supply Fan operation. This is useful when you
are using multiple VCM-X / RNE-controlled HVAC units and want to
be sure that all the units do not start at exactly the same time when the
Occupied schedule occurs. Each VCM-X or RNE should be set with
staggered Fan Starting Delay Timer Setpoint values. When the 255
Second default setpoint is used, it multiplies each VCM-X or RNE’s
address by 5 and uses this value in seconds as the Fan Starting Delay
Time. This provides a staggered start for each VCM-X or RNE on the
system without having to individually set each VCM-X or RNE for its
own time delay.

Description

Minimum

Default

Maximum

Fan Start Delay Timer

0 Sec

255 Sec

255 Sec

Setpoint Screen #27 - Mechanical Heat/Cool

Failure Time Period

VCM-X / RNE Spts

Mechanical Heat/Cool

Failures Occur After
No Change For 15 Min

When Heating or Cooling Mode is initiated and staging is activated, if the
Supply Air Temperature does not rise or fall 5°F within the Mechanical
Heat/Cool Failures Occur After No Change For Setpoint time period,
a Mechanical Heating or Cooling failure alarm will be generated. The
Alarm is for Status Reporting only. The HVAC unit will continue to run.

Description

Minimum

Default

Maximum

Mechanical Heat/Cool

Failures Occur After

No Change For

0 Min

15 Min

255 Min

Setpoint Screen #28 - Preheat/ Low Ambient

Temperature

VCM-X / RNE Spts

Preheat/Low

Ambient Temperature

Setpoint: 0ºF

For cold climates where freezing temperatures may be experienced,
a Pre-Heater relay output can be activated based on the Outdoor Air
Temperature to prevent freezing of Water Coils. One of the VCM-X
/ RNE Relay Outputs must be confi gured for the Pre-Heater control.
When confi gured, if the Outdoor Air Temperature falls below the Low
OAT Ambient Protection Temperature Setpoint and the HVAC unit is
in Occupied Mode, the Pre-Heater relay will activate.

Description

Minimum

Default

Maximum

Preheat/Low Ambient

Temperature

0ºF

0ºF

70ºF

Setpoint Screen #29 - Max OA Damper

Tempering Limit

VCM-X / RNE Spts

Max OA Damper

Tempering Limit
Setpoint: 50%

The Maximum OA Damper Tempering Limit Setpoint allows you to
set the maximum damper position the economizer can open to while
the heat is running during the VAV Supply Air tempering mode in this
sequence (to prevent potential wasting of energy).

Description

Minimum

Default

Maximum

Maximum Outdoor Air

Damper Tempering Limit

0%

50%

60%

Setpoint Screen #30 - HVAC Schedule

VCM-X / RNE Spts

HVAC Schedule...: 0

[ 0 = Internal ]
[1-5 = External ]

The VCM-X / RNE has an Internal Scheduler. If you want the VCM-X or
RNE to use its own Internal Schedule to schedule the HVAC unit, enter

<0>

for Internal. To use the External Schedule option, you must have a

GPC Plus controller installed and operating on your system. To use one
of the (5) External Schedules available on the GPC Plus controller, enter
the number of the GPC Plus Schedule (1 through 5) you wish to use.

Description

Minimum

Default

Maximum

HVAC Schedule

0

0

5

VCM-X / RNE Setpoint Screens

Advertising
This manual is related to the following products: