Minilink pd programming, Minilink pd confi guration screens, Vcm-x / rne operator interfaces technical guide 66 – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 66: Minilink pd confi guration

Advertising
background image

MINILINK PD PROGRAMMING

VCM-X / RNE Operator Interfaces Technical Guide

66

MiniLink PD Confi guration Screens

MiniLink PD Confi guration

In order to correctly setup the MiniLink PD, you must fi rst confi gure
several parameters in regard to the type of system and operating param-
eters for the system it is installed on. Most of these values and operating
parameters are only set once at the initial system setup and are never
changed.

System Manager Instructions

From any Menu Screen, press the

<SETPOINTS>

button. The Unit

Selection Screen will appear requesting that you enter the unit ID num-
ber. All MiniLink PDs are set at address 60. Enter the correct unit loop
number for the loop the MiniLink Polling Device is connected to (Loop
1 you would enter 1) and then enter

<60>

. Press

<ENTER>

. You will

see the screen shown below.

1) Change Setpoint
2) Configure Unit
3) Damper Force

ESC) Exit Menu

Press

<2>

on the keypad to enter the fi rst Unit Confi guration Screen.

Modular Service Tool Instructions

From any Menu Screen, press the

<CONFIGURATION>

button. The

Unit Selection Screen will appear requesting that you enter the unit ID
number. Enter the correct unit ID number of the controller you want to
confi gure and press

<ENTER>

. You will then see Unit Confi guration

Screen #1.

Confi guration Screen #1 - System Type

Polling Unit Config

System Type

Selection: X

[0=Zoning 1=VAV]

This screen allows you to select whether you want the system to behave
as a VAV system or a Zoning System. If you select VAV, this will allow
tenant logging for your VAV system.

Confi guration Screen #2 - Last Polled Zone

Polling Unit Config

Last Polled Zone

Address: XX

[Enter Last Zone]

This zone is the last zone on the local loop of your zoning system that
is to be included in zone voting.

Confi guration Screen #3 - Mode Changeover

Time

Polling Unit Config

Mode Changeover Time

Minutes: XX

[Enter Period Time]

This is the amount of time that you want to allow between changeover
from heating to cooling modes.

Confi guration Screen #4 - Optimal Start

Target Zone

Polling Unit Config

Optimal Start

Target Zone..: XXX

[Enter Target Zone]

This is the unit ID of the Zone that you want to be satisfi ed by the normally
scheduled start time. If you enter “-1” into this box, it will average all
zones instead of picking a specifi c zone. If you do not require Optimal
Start, enter “0”.

Confi guration Screen #5 - Maverick Testing

Polling Unit Config

Maverick Testing

Disabled: YES
[0=NO 1=YES]

Disabling the Maverick Testing allows known troubled zone(s) to con-
tinue voting without causing a Maverick alarm. In other words, all zones
are included in the voting regardless of whether they are more than four
degrees from setpoint.

Confi guration Screens #6-65 - Alarm Polling

Polling Unit Config

Enable Alarm Polling

Unit XX : YES
[0=NO 1=YES]

Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.