VCM-X / RNE STATUS

VCM-X / RNE Operator Interfaces Technical Guide

51

VCM-X / RNE Status Screens

Status Screen 8 - Coil Temp & Setpoint

VCM-X / RNE v1.00

Coil Tmp...: XX.XºF
Coil Tmp Spt: XX.XºF

Line 2 Coil Temperature or Lowest Coil

If a Suction Pressure Transducer has been installed and

confi gured on the unit, the calculated Evaporator Coil

Temperature will appear on this line. If not, this line will

display

0°F.

If this unit has multiple digital scroll compressors and has a

Full Digital Module or Dual Digital Module installed, this

line will display Lowest Coil and will display the lowest of

the multiple suction temperatures. The coil temperatures of

all the coils will be displayed on Status Screens 19 & 20.

Line 3 Coil Temperature Setpoint

During

dehumidifi cation, the Coil Suction Temperature

Setpoint is automatically reset based on the current space

humidity conditions. This is the current calculated Coil

Temperature Setpoint based on that reset.

Status Screen 9 - Outdoor Air Temperature &

Outdoor Air Relative Humidity

VCM-X / RNE v1.00

Outdoor Tmp: XX.XºF
Outdoor RH.: XX.X%

Line 2 Current Outdoor Air Temperature

If an Outdoor Air Temperature Sensor has been installed

and

confi gured on the unit or if an Outdoor Air Broadcast

has

been

confi gured on another VCM-X or RNE Controller

on the system, the Outdoor Air Temperature will appear on

this line. If not, this line will display a temperature that is

half way between the Cooling and Heating Lockout

Setpoints.

Line 3 Current Outdoor Air Relative Humidity

If an Outdoor Humidity Sensor has been installed and

confi gured on the VCM-X or RNE, the Outdoor Air

Relative Humidity Percentage will appear on this line. If

not, this line will display 0%.

Status Screen 10 - OA Dewpoint & Dewpoint

Temp

VCM-X / RNE v1.00

OA Dewpoint.: XX.XºF
Dewpoint Spt: XX.XºF

Line 2 Current Calculated Outdoor Air Dewpoint
Temperature

If both an Outdoor Humidity Sensor and an Outdoor Air

Temperature Sensor have been installed and confi gured on

the unit, the calculated Outdoor Air Dewpoint Temperature

will appear on this line. If not, this screen displays 0°F.

Line 3 Current Outdoor Air Dewpoint Setpoint

The user adjustable Outdoor Air Dewpoint Temperature

Setpoint will appear on this line.

Status Screen 11 - Indoor RH & Indoor RH

Setpoint

VCM-X / RNE v1.00

Indoor RH....: XXX%
Indoor RH Spt: XXX%

Line 2 Current Indoor Relative Humidity Percentage

If an Indoor Humidity Sensor has been installed and

confi gured on the unit, the current Indoor Air Relative

Humidity Percentage will appear on this line. The installed

Indoor Humidity Sensor can be either a Wall Mounted type

or a Return Air Mounted type. If an Indoor Humidity

Sensor is not installed, this line will display 0%.

Line 3 Current Indoor Relative Humidity Setpoint Percentage

This is the adjustable Indoor Air Relative Humidity

Setpoint Percentage that has been set by the user.