VCM-X / RNE / VAV/Zone Damper Force Modes

Damper Force Modes

Damper Force Modes are available for testing or balancing the system.
These Force Modes can be accessed and programmed from either the
System Manager or Modular Service Tool.

System Manager Instructions

To access the Damper Force Modes from the System Manager, press

<SETPOINTS>

. You will then see the Unit ID Screen. Enter the unit

ID of the controller you wish to access and press

<ENTER>

. The fol-

lowing screen will appear:

1) Change Setpoint
2) Configure Unit
3) Dampers Force

ESC) Exit Menu

Press

<3>

on the keypad and then press

<ENTER>

. You will then see

the Unit ID Screen. Enter the unit ID of the controller you wish to access
and press

<ENTER>

. At this time the Passcode Screen will be displayed.

Enter your level 2 passcode. Press

<ENTER>

and the Damper Force

Modes Screen will be displayed.

Modular Service Tool Instructions

When using the Modular Service Tool, simply press the

<BALANCE -

TEST>

key. You will then see the Unit ID Screen. Enter the unit ID of

the controller you wish to access and press

<ENTER>

. The following

screen will be displayed:

1) Outputs Force
2) Dampers Force

ESC) Exit Menu

Press

<2>

to access the Dampers Force Mode Screen.

Dampers Force Mode Screen
If the unit ID you entered is for a VCM-X or RNE Controller that has
VAV/Zone Controllers connected to its communication loop, the Damper
Force Mode will act as a “Global” Damper Force Mode. That is, all VAV/
Zone Controllers on that VCM-X or RNE Controller’s communication
loop will be forced to the same Damper Force Mode setting. If the unit
ID you entered is for a VAV/Zone Controller, the Damper Force Mode
setting will only apply to that VAV/Zone Controller.

Damper Force

Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed

Set the appropriate Damper Force Mode by entering numbers 0 through
5. Following is a list of the force modes and their meaning:

0 = Auto

This is the default setpoint. With this setting,

the damper will operate normally and modulate

according to the controller setpoints.

1 = Open

This setting will force the dampers to their fully-

open

position.

2 = Clsd

This setting will force the damper to its fully-

closed

position.

3 = Max

This setting will force the damper to its

Maximum

Position

Setpoint.

See

VAV/Zone

Controller

Setpoint

Screen

#5 on page 60 for

complete

setpoint

information.

4 = Min

This setting will force the damper to its Minimum

Position

Setpoint.

See

VAV/Zone Controller

Setpoint

Screen

#5 on page 60 for complete

setpoint

information.

5 = Fixed

This setting will force the damper to a fi xed

position based on the Fixed Position Setpoint.

See

VAV/Zone Controller Setpoint Screen #8

on page 61 for complete setpoint information.

CAUTION: The Damper Force Modes should only be used

by qualifi ed service personnel. Serious damage to
the ductwork could result if the dampers are all
forced closed and the HVAC unit fan is operating.