VCM-X / RNE Operator Interfaces Technical Guide

RNE CONFIGURATION

29

RNE Confi guration Screens

Confi guration Screens

In order to correctly set up the RNE Controller, you must fi rst confi gure
several parameters in regard to the type of HVAC unit and system you
have installed. Most of these values and operating parameters are only
set once at the initial system setup and are never changed.

No matter what screen or menu you’re in, press

<CONFIGURATION>

.

The Unit Selection Screen will appear, requesting that you enter the
unit ID number.

Unit Selection
Enter Unit ID#

Selected ID#: XXXX

Enter the correct unit ID number of the RNE Controller you want to
confi gure and press

<ENTER>

. You will then see Unit Confi guration

Screen #1.

Confi guration Screen #1 - Duct Static

Pressure

RNE Cnfg ID 101

Duct Static Pressure

Control: YES
[0=NO 1=YES]

If the HVAC unit has a Supply Fan that delivers a Constant Volume of
air, enter

<0>

for NO. If the HVAC unit has a Supply Fan that delivers

a Variable Volume of Air using a VFD or a Bypass Damper, enter

<1>

for YES. Default is YES.

Confi guration Screen #2 - Supply Fan Cycle

RNE Cnfg ID 101

Supply Fan Cycle

Mode: NO

[0=NO 1=YES]

If you want the HVAC unit’s Supply Fan to run during Heating, Cool-
ing, or Dehumidifi cation Modes, enter

<1>

for YES. If you want the

HVAC unit’s Supply Fan to run continuously while in the Occupied
Mode, regardless of the Heating, Cooling, or Dehumidifi cation Modes,
enter

<0>

for NO. Default is NO.

Confi guration Screen #3 - HVAC Mode Enable

RNE Cnfg ID 101

HVAC Mode Enable

Supply Air

Press “0” to Change

Enter

<0>

to select the Temperature Sensor that will determine the Heat-

ing, Cooling, or Vent Mode of operation. The selections are:

 

Supply Air

This is typical for VAV applications. Occupied Cooling

with

Morning

Warm-up.

Outdoor

Air

This is for 100% Outdoor Air (MUA) units.

Dehumidifi cation utilizes a Dewpoint Calculation if

equipped with an Outdoor Air Humidity Sensor.

Space

Temperature

This is for any unit that conditions a space and is not 100%

Outdoor air. Occupied/Unoccupied Heating, Cooling, and

Vent Modes of operation.

Return

Air

This selection can be used when an Average Building

Temperature (the Return Air Temperature) needs to

determine Heating, Cooling, and Vent Modes of operation.

Supply Air/Tempering

This selection is for VAV “cooling only” applications where

because of cold outdoor temperatures, even at minimum

damper position, you may need to enable heat to maintain

the cooling near its Cooling Supply Air Setpoint. When

heat is enabled during this sequence, it will control to

a non-adjustable setpoint that is 2ºF less than the Cooling

Supply Air Setpoint. Includes a Morning Warm-up

sequence.

Confi guration Screen #4 - HVAC Reset Source

RNE Cnfg ID 101

HVAC Reset Source

No Reset

Press “0” to Change

The Supply Air Heating and Cooling Temperature Setpoints can be reset
using various input sources. Default is No Reset. Press

<0>

to change/

select the desired Reset Source for Supply Air Temperature Reset. The
Single Zone VAV option should be selected in applications where the
Supply Fan VFD speed is reset based on the Space Temperature. If you
select No Reset, then neither the Supply Air Setpoint nor the Supply
Fan VFD Reset will occur. The selections are:

No Reset

Fan VFD Percentage

Sp

ace Sensor

Outdoor Sensor

Return Air Sensor

Single Zone (SZ) VAV

Remote Reset Signal

SZ VAV with CV Heating