Rne configuration, Rne confi guration screens, Vcm-x / rne operator interfaces technical guide 32 – Orion System VCM-X/RNE Operator Interfaces User Manual

Page 32

Advertising
background image

RNE CONFIGURATION

VCM-X / RNE Operator Interfaces Technical Guide

32

Confi guration Screen #19 - RNE Tonnage

RNE Cnfg ID 101

RNE Tonnage

55–75 Tons

[Press ‘0’ to Change]

Press

<0>

to change/select the desired Tonnage. Default is 55–75 Tons.

The selections are:

55–75 Tons

95–105 Tons

120–140 Tons

Confi guration Screen #20 - Water Source Heat

Pump Installed

RNE Cnfg ID 101

Water Source

Heat Pump: NO

[0=NO 1=YES]

Enter

<1>

for YES if this is a Water Source Heat Pump. Enter

<0>

for

NO. Default is NO.

Confi guration Screen #21 - Modulating Cool-

ing Reverse Acting

RNE Cnfg ID 101

Mod Cooling

Rev Acting: NO

[0=NO 1=YES]

Enter

<1>

for YES if the Modulating Cooling Source requires 0 VDC

to open and 10 VDC to close. You cannot use a Reverse Acting Signal
if a VFD Compressor is being used. Enter

<0>

for NO. Default is NO.

Confi guration Screen #22 - Modulating Cool-

ing Proportional Window

RNE Cnfg ID 101
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s

The Modulating Cooling Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The Time Period
is the delay before another signal increase or decrease can be made
and is user-adjustable. Short Time Periods may cause hunting of the
Modulating Signal. Defaults are 10ºF and 30 seconds.

RNE Confi guration Screens

Confi guration Screen #23 - Head Pressure

Module Installed

VCMX-M/HP Cnfg ID 102

Head Pressure

Module Installed: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have a Head Pressure Module installed.

Enter

<0>

for NO. This screen only applies if using the RNE Modular

or WSHP Controller. Default is NO.

Confi guration Screen #24 - Monitor Outdoor

Air CFM

RNE Cnfg ID 101
Monitor Outdoor

Air CFM: NO

[0=NO 1=YES]

Enter

<1>

for YES if you have an Airfl ow Monitoring station measur-

ing the CFM of the Outdoor airfl ow stream of this unit. Enter

<0>

for

NO. Default is NO.

Confi guration Screen #25 - Control Outdoor

Air CFM

RNE Cnfg ID 101

Control Outdoor

Air CFM: NO

[0=NO 1=YES]

Enter

<1>

for YES if you want to control the Outdoor Air Damper to

a CFM setpoint. Enter

<0>

for NO. Default is NO.

Confi guration Screen #26 - Outdoor Duct/

Damper Size

RNE Cnfg ID 101

Outdoor Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the outside air CFM you need
to enter the inside area (sq. ft.) of the outdoor air duct/damper. When
measuring the outdoor air damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.