Installation, 2 electrical installation, 1 power connections – LEESON SM4 Series Flux Vector User Manual

Page 12: Installation after a long period of storage

Advertising
background image

11

Installation

174603

174604

174605

174651

174652

174653

174654

3.2.1

Power Connections

DANGER!

Hazard of electrical shock! Circuit potentials are up to 600 VAC above earth ground.

Capacitors retain charge after power is removed. Disconnect power and wait at

least three minutes before servicing the drive.

STOP!

• Verify mains voltage before connecting to drive.

• Do not connect mains power to the output terminals (U,V,W)! Severe damage to

the drive will result.

• Do not cycle mains power more than once every two minutes. Damage to the

drive will result.

Mains and Motor Terminations

Type

Torque

Strip Length

174991, 174992

24 lb-in (2.7 Nm)

7/16 in (10mm)

174710, 174711

27 lb-in (3.05 Nm) 0.75 in (19mm)

3.2.1.1 Mains connection to 120VAC Single-Phase Supply

PE L1 L2 N

PE L1

N

3.2

Electrical installation

Installation After a Long Period of Storage

STOP!

Severe damage to the drive can result if it is operated after a long period of storage

or inactivity without reforming the DC bus capacitors.
If input power has not been applied to the drive for a period of time exceeding

three years (due to storage, etc.), the electrolytic DC bus capacitors within the

drive can change internally, resulting in excessive leakage current. This can result in

premature failure of the capacitors if the drive is operated after such a long period

of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long

period of inactivity, apply input power to the drive for 8 hours prior to actually

operating the motor.