5

Technical data

2

Technical data

2.1

Standards and application conditions

Conformity

CE

Low Voltage Directive (73/23/EEC)

Approvals

UL 508C

Underwriters Laboratories - Power Conversion Equipment

Input voltage phase imbalance

< 2%

Supported Power Systems

TT

TN

– For central grounded systems, operation is

permitted without restrictions.

– For corner grounded 400/500V systems, operation

is possible but reinforced insulation to control

circuits is compromised.

Humidity

< 95% non-condensing

Temperature range

Transport

-25 … +70°C

Storage

-20 … +70°C

Operation

-10 … +55°C

(with 2.5%/°C current derating

above +40°C)

Installation height

0 … 4000m a.m.s.l.

(with 5%/1000 m current derating above 1000m a.m.s.l.)

Vibration resistance

acceleration resistant up to 1.0g

WARNING!

Earth leakage current

> 3.5 mA to PE

Max Permissable Cable Length

(1)

<=4.0 Hp (3.0 kW) 30 meters shielded, 60 meters un-shielded
=> 5.0 Hp (3.7 kW) 50 meters shielded, 100 meters un-shielded

Enclosure

IP31 / NEMA 1

IP65/NEMA 4X

NEMA 1 and NEMA 4X model enclosures are plenun rated in accordance

with UL 508C and are suitable for installation in a compartment handling

conditioned air.

Protection measures against

short circuit, earth fault, phase loss, over voltage, under voltage, motor

stalling, over temperature, motor overload

Compliance with EN 61000-3-2

Requirements

(2)

< 0.5 kW

with mains choke

0.5 ... 1 kW

with active filter

> 1 kW

without additional measures

Compliance with EN 61000-3-12

Requirements (2)

16 ... 75 amp

Additional measures required for compliance with

EN 61000-3-12

Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic

Compatibiliy (EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).

(1) The stated cable lengths are permissiable at default carrier frequencies (refer to parameter P166).

(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.

The machine/system manufacturer is responsible for the machine’s compliance with the regulations.