Installation – LEESON SM4 Series Flux Vector User Manual

Page 16

Advertising
background image

15

Installation

3.2.2

Fuses/cable cross-sections

Note

Observe local regulations.

Local codes may supersede these recommendations

Type

Recommendations

Fuse

Miniature

circuit

breaker

(1)

Fuse

(2)

or

Breaker

(3)

(N. America)

Input Power Wiring

(L1, L2, L3, PE)

[mm²]

[AWG]

120V

1~

(1/N/PE)

174603

M10 A

C10 A

10 A

1.5

14

174604, 174652.00

M16 A

C16 A

15 A

2.5

14

174605, 174653.00

M25 A

C25 A

25 A

4

10

240V

1~

(2/PE)

174603, 174604,174652, 174653

174607, 74606

M10 A

C10 A

10 A

1.5

14

174605, 174608

M16 A

C16 A

15 A

2.5

14

174609, 174651, 174654, 174657

M20 A

C20 A

20 A

2.5

12

174610, 174658

M25 A

C25 A

25 A

2.5

12

174611, 174659

M32 A

C32A

32 A

4

10

240V

3~

(3/PE)

174607, 174608, 174606

M10 A

C10 A

10 A

1.5

14

174609, 174610, 174612, 174613

174651, 174654, 174657, 174658

M16 A

C16 A

12 A

1.5

14

174611, 174614, 74659

M20 A

C20 A

20 A

2.5

12

174615, 174660

M32 A

C32 A

32 A

4.0

10

174616, 174661

M40 A

C40 A

35 A

6.0

8

174617, 174662

M50 A

C50 A

45 A

10

8

174618

M80 A

C80 A

80 A

16

8

174619

M100A

C100A

90 A

16

8

400V

or 480V

3~(3/

PE)

174620, 174624, 174671, 174675

M10 A

C10 A

10 A

1.5

14

174625, 174676

M16 A

C16 A

20 A

2.5

14

174626, 174677

M20 A

C20 A

20 A

2.5

14

174627, 174678

M25 A

C25 A

25 A

4.0

10

174628

M40 A

C40 A

40 A

4

8

174629

M50 A

C50 A

50 A

10

8

174630

M63 A

C63 A

70 A

10

6

174991

M80 A

C80 A

80 A

16

6

174992

M100 A

C100 A

100 A

25

4

174710

M125 A

C125 A

125 A

35

2

174711

M180 A

C160 A

150 A

35

1

600V

3~(3/

PE)

174631, 174632, 174633,

174663, 174665

M10 A

C10 A

10 A

1.5

14

174634, 174666

M16 A

C16 A

12 A

1.5

14

174635, 174667

M16 A

C16 A

15 A

2.5

14

174636, 174668

M20 A

C20 A

20 A

2.5

12

174637

M32 A

C32 A

30 A

4

10

174638

M40 A

C40 A

40 A

4

8

174639

M50 A

C50 A

50 A

6

8

174993

M63 A

C63 A

60 A

10

8

174994

M80 A

C80 A

70 A

16

6

174712

M100 A

C100 A

90 A

16

4

174713

M125 A

C125 A

110 A

25

2

(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.

(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.

(3) Thermomagnetic type breakers preferred.